DVC6200f Digital Valve Controller
Label
PARAMETER_NAME
Output Scale
OUT_SCALE
Grant Deny
GRANT_DENY
GRANT
DENY
I/O Options
4
IO_OPTS
Status Options
STATUS_OPTS
AI Channel
CHANNEL
Linearization Type
L_TYPE
Low Cutoff
LOW_CUT
Process Value Filter Time
PV_FTIME
Field Value
FIELD_VAL
Updated Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
164
Table 4-57. Analog Input Block Parameter Definitions
Index
RO /
Write Block
Number
RW
Mode
EU at 100%
EU at 10%
11
OOS
Units Index
Decimal Point
12
Valid Bits
12.1
ALL
0: Program
1: Tune
2: Alarm
12.2
ALL
3: Local
13
OOS
10: Low cutoff
3: Propagate Failure
forward
6: Uncertain if Limited
14
OOS
7: Bad if Limited
8: Uncertain in Man
Mode
15
OOS
See table 4-54
0: Undefined
1: Direct
16
OOS, MAN
2: Indirect
3: Ind. Sqr. Root
17
ALL
Positive
18
ALL
Positive
19
RO
20
0
Undefined
=
20.1
RW
N/A
1
Acknowledged
=
2
Unacknowledged
=
0
Undefined
=
20.2
RO
N/A
1
Update reported
=
2
Update not reported
=
20.3
RO
N/A
20.4
RO
N/A
20.5
RO
N/A
Initial
Range
Value
Data Type: DS-68
100
The high and low scale values, engineering units
0
code, and number of decimal places to be used in
%
displaying the OUT parameter and parameters
2
which have the same scaling as OUT.
Data Type: DS-70
Options for controlling access of host computer
and local control panels to operating, tuning, and
All bits: 0
alarm parameters of the block.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
All bits: 0
Data Type: Bit String
0=Disable
All bits: 0
1=Enable
User options for Output Control.
Data Type: Bit String
0=Disable
All bits: 0
1=Enable
User options for Status
Data Type: Unsigned16
Used to select the type of threshold that is used to
0: Undefined
set the output.
Data Type: Enum
Linearization type. Determines whether the field
value is used directly (Direct), is converted linearly
(Indirect), or is converted with the square root
0: Undefined
(Indirect Square Root). The OUT_SCALE is
normally the same as the transducer, but if
L_TYPE is set to Indirect or Ind Sqr Root,
OUT_SCALE determines the conversion from
FIELD_VAL to the output.
Data Type: Float
0
If calculated output is below this value the output is
0.
Data Type: Float
Time constant of first order filter on PV, in
0
seconds.
Data Type: DS-65
0
Value of the field device analog input, with a status
reflecting the Transducer condition.
0
Undefined
=
Data Type: DS-73
This alarm is generated whenever a static
0
Undefined
=
parameter is changed.
0
0
0
−Continued−
Description
November 2010