DVC6200f Digital Valve Controller
Label
PARAMETER_NAME
PD Detail 1 Active
PD_DETAIL1_ACTIVE
4
PD Detail 2 Active
PD_DETAIL2_ACTIVE
PD Detail 3 Active
PD_DETAIL3_ACTIVE
PD Detail 4 Active
PD_DETAIL4_ACTIVE
84
Table 4-14. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
0: I/P Primary Plugged
1: I/P Nozzle Plugged
2: I/P Latched
3: Reserved
4: Relay Jammed
5: Relay Cross Misadj
6: Relay Bias Diaph
Leak
7: Relay Port A Diaph
Leak
8: Relay Port B Diaph
Leak
9: Reserved
(1)
74.9
RO
ALL
10: Valve Stuck Low or
Sensor Arm Damage
11: Valve Stuck High or
Sensor Arm Damage
12: Piston Ring Leak
13: Reserved
14: Low Supply
Pressure
15: External Leak
16: SOV Trip
17: Air Line Blocked
18: Reserved
19: Reserved
20: Unknown
(1)
74.10
RO
ALL
Reserved
0: I/P Primary Plugging
1: I/P Nozzle Plugging
2: I/P Calibration Shift
3: Reserved
4: Relay Cross Misadj
5: Relay Port A Diaph
Leak
6: Relay Port B Diaph
Leak
7: Reserved
8: Piston Ring Leak
(1)
74.11
RO
ALL
9: Reserved
10: Reserved
11: Low Supply
Pressure
12: Reserved
13: External Leak
14: Reserved
15: Travel Calibration
Shift
16: Unknown
17: Reserved
18: Reserved
(1)
74.12
RO
ALL
Reserved
−Continued−
Protect
Initial Value
Category
Data Type: Bit String (4 byte)
0=inactive
All bits:0
N/A
1=active
Performance Diagnostic Critical
possible cause.
Data Type: Bit String (4 byte)
0=inactive
All bits: 0
N/A
1=active
Performance Diagnostic Detail
status.
Data Type: Bit String (4 byte)
0=inactive
1=active
All bits: 0
N/A
Performance Diagnostic Reduce
possible cause.
Data Type: Bit String (4 byte)
0=inactive
All bits: 0
N/A
1=active
Performance Diagnostic Detail
status
Description
November 2010