Label
Index
PARAMETER_NAME
Number
Deviation High Priority
56
DV_HI_PRI
Deviation High Limit
57
DV_HI_LIM
Deviation Low Priority
58
DV_LO_PRI
Deviation Low Limit
59
DV_LO_LIM
High High Alarm
60
HI_HI_ALM
UNACKNOWLEDGED
60.1
ALARM_STATE
60.2
TIME_STAMP
60.3
SUBCODE
60.4
VALUE
60.5
High Alarm
61
HI_ALM
UNACKNOWLEDGED
61.1
ALARM_STATE
61.2
TIME_STAMP
61.3
SUBCODE
61.4
VALUE
61.5
Low Alarm
62
LO_ALM
UNACKNOWLEDGED
62.1
ALARM_STATE
62.2
TIME_STAMP
62.3
SUBCODE
62.4
VALUE
62.5
Low Low Alarm
63
LO_LO_ALM
UNACKNOWLEDGED
63.1
ALARM_STATE
63.2
TIME_STAMP
63.3
SUBCODE
63.4
VALUE
63.5
November 2010
Table 4-32. PID Function Block System Parameters Definitions
RO /
Block
Range
RW
Mode
ALL
0 to 15
ALL
PV_SCALE, or +INF
ALL
0 to 15
−INF, or −PV span to 0
ALL
0=Undefined
1=Acknowledged
RW
N/A
2=
Unacknowledged
0=Undefined
1=Clear reported
RO
N/A
2=Clear not reported
3=Active reported
4=Active not reported
RO
N/A
RO
N/A
RO
N/A
0=Undefined
RW
N/A
1=Acknowledged
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
RO
N/A
3=Active reported
4=Active not reported
RO
N/A
RO
N/A
RO
N/A
0=Undefined
RW
N/A
1=Acknowledged
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
RO
N/A
3=Active reported
4=Active not reported
RO
N/A
RO
N/A
RO
N/A
0=Undefined
RW
N/A
1=Acknowledged
2=
Unacknowledged
0=Undefined
1=Clear reported
RO
N/A
2=Clear not reported
3=Active reported
4=Active not reported
RO
N/A
RO
N/A
RO
N/A
−Continued−
PID Function Block
Initial Value
Description
Data Type: Unsigned8
0
The priority of the deviation high alarm.
Data Type: Float
+INF
The setting for the alarm limit used to detect the
deviation high alarm condition.
Data Type: Unsigned8
0
The priority of the deviation low alarm.
Data Type: Float
−INF
The setting for the alarm limit use to detect the
deviation low alarm condition.
0=undefined
Data Type: DS-71
The HI HI alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
0=undefined
VALUE Data Type: Float
0
0
0
0=undefined
Data Type: DS-71
The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state
of the alarm.
0=undefined
VALUE Data Type: Float
0
0
0
0=undefined
Data Type: DS-71
The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state
of the alarm.
0=undefined
VALUE Data Type: Float
0
0
0
0=undefined
Data Type: DS-71
The LO LO alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
0=undefined
VALUE Data Type: Float
0
0
0
4
123