DVC6200f Digital Valve Controller
Resource Block Parameter List
D Read/Write Capability: RO − Read Only, RW − Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub-parameter.
Label
PARAMETER_NAME
Static Revision
ST_REV
4
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET_MODE
ACTUAL_MODE
PERMITTED_MODE
NORMAL_MODE
Block Error
BLOCK_ERR
Device State
RS_STATE
Test Read Write
TEST_RW
DD Resource
DD_RESOURCE
40
Table 4-3. Resource Block Parameter Definitions
Index
RO /
Mode
Range
Number
RW
1
RO
NA
0 to 65535
2
RW
NA
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
3: Auto
5.1
RW
ALL
7: OOS
3: Auto
6: IMAN (only during
5.2
RO
NA
initialization
7: OOS
3: Auto
5.3
RW
ALL
7: OOS
5.4
RW
ALL
3: Auto
0: Other
1: Block
Configuration Error
3: Simulate Active
6: Device needs
Maintenance Soon
9: Memory Failure
6
RO
N/A
10: Lost Static Data
11: Lost Non-Volatile
Memory
13: Device needs
Maintenance Now
14: Power-up
15: Out-of-
Service (MSB)
2: Initialization,
Actual mode=IMAN
4: On-line, Actual
Mode=Auto
7
RO
N/A
5: Standby, Actual
Mode=OOS
6: Failure, Actual
Mode=OOS
8
ALL
9
RO
N/A
−Continued−
Initial
Description
Value
Data Type: Unsigned16
The revision level of the static data. Increments
by one each time a static parameter changes.
0
The value is reset to 0 whenever a Restart with
Defaults is performed. See Restarting the
Instrument.
Data Type: Octet String
The user description of the intended application
Spaces
of the block. Null characters are not allowed in
this data type.
Data Type: Unsigned16
0
Used to identify groupings of blocks. The data
is not checked or processed by the block.
Data Type: Unsigned8
The identification number of the plant unit.
0
Devices in a loop or plant section can be
assigned with a common alert key to aid the
operator in determining location of alerts.
3: Auto
Data Type: DS-69
The actual, target, permitted, and normal
modes.
N/A
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
3: Auto
Normal: Most common mode for Target
7: OOS
3: Auto
Data Type: Bit String
0 = Inactive
1 = Active
Dynamic
Error status associated with hardware or
software for the resource block. When an error
is shown it may be broadcast to the host
through BLOCK_ALM.
Data Type: Unsigned8
5: Standby
State of the function block application state
machine.
This parameter may be used in interoperability
testing to read and write all standard data
0
types supported by the Fieldbus Foundation.
Data Type: Visible String
String identifying the VFD tag of the resource
Spaces
that contains the Device Description for this
resource.
November 2010