Table 4-40. Input Selector Function Block Parameter Definitions (Continued)
Label
Index
PARAMETER_NAME
Number
Disable Analog Input 8
DISABLE_8
Number used to average
AVG_USE
Alarm Summary
ALARM_SUM
CURRENT
34.1
34.2
UNACKNOWLEDGED
34.3
UNREPORTED
34.4
DISABLED
Acknowledge Option
ACK_OPTION
Alarm Hysteresis
ALARM_HYS
High High Priority
HI_HI_PRI
High High Limit
HI_HI_LIM
High Priority
HI_PRI
High Limit
HI_LIM
Low Priority
LO_PRI
Low Limit
LO_LIM
Low Low Priority
LO_LO_PRI
Low Low Limit
LO_LO_LIM
High High Alarm
HI_HI_ALM
UNACKNOWLEDGED
45.1
ALARM_STATE
45.2
TIME_STAMP
45.3
SUBCODE
45.4
VALUE
45.5
November 2010
RO /
Block
RW
Mode
Value
32
ALL
Status
0=Use
1=Disable
33
1 to 8
34
RO
NA
1: Hi Hi
RO
NA
2: Hi
RO
NA
3: Lo Lo
4: Lo
RW
ALL
1: Hi Hi
2: Hi
35
ALL
3: Lo Lo
4: Lo
36
ALL
0 to 50%
37
ALL
0 TO 15
38
ALL
39
ALL
0 TO 15
40
ALL
41
ALL
0 TO 15
42
ALL
43
ALL
0 TO 15
44
ALL
45
0=Undefined
RW
N/A
1=Acknowledged
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
RO
N/A
3=Active reported
4=Active not
reported
RO
N/A
RO
N/A
RO
N/A
ISEL Function Block
Initial
Range
Value
BAD
NC
Data Type: DS-66
constant
Enable/Disable for Input_8, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
0
Data Type: Unsigned8
Number used to average the output. The number of
0
min and max dropped is the number of inputs minus
AVG_USE.
Data Type: DS-74
Current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
Data Type: Bit String
Selection of whether alarms associated with the block
0
will be automatically acknowledged.
0=Disable
1=Enable
Data Type: Float
0.50%
Hysteresis on alarms
Data Type: Unsigned8
0
Priority of the alarm
Data Type: Float
0
Value of analog input which will generate an alarm
Data Type: Unsigned8
0
Priority of the alarm
Data Type: Float
0
Value of analog input which will generate an alarm
Data Type: Unsigned8
0
Priority of the alarm
Data Type: Float
0
Value of analog input which will generate an alarm
Data Type: Unsigned8
0
Priority of the alarm
Data Type: Float
0
Value of analog input which will generate an alarm
0
Data Type: DS-71
The high high alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the state
0
of the alarm.
0
0
0
−Continued−