Label
Index
PARAMETER_NAME
Number
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Alarm Summary
ALARM_SUM
CURRENT
UNACKNOWLEDGED
UNREPORTED
D ISABLED
Acknowledge Option
ACK_OPTION
Alarm Hysteresis
ALARM_HYS
High High Priority
HI_HI_PRI
High High Limit
HI_HI_LIM
High Priority
HI_PRI
Hi Limit
HI_LIM
Low Priority
LO_PRI
Low Limit
LO_LIM
Low Low Priority
LO_LO_PRI
Low Low Limit
LO_LO_LIM
High High Alarm
HI_HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
High Alarm
HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
November 2010
Table 4-57. Analog Input Block Parameter Definitions
RO /
Write Block
RW
Mode
21
0
Undefined
=
21.1
RW
1
Acknowledged
=
2
Unacknowledged
=
0
Undefined
=
1
Clear-reported
=
2
Clear-not reported
21.2
RO
=
3
Active-reported
=
4
Active-not reported
=
21.3
RO
21.4
RO
21.5
RO
22
22.1
RO
ALL
0: Discrete alarm
1: Hi Hi alarm
22.2
RO
ALL
2: Hi Alarm
3: Lo Lo Alarm
22.3
RO
ALL
4: Lo Alarm
22.4
RW
ALL
7: Block alarm
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
23
ALL
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
0 − 50%
24
ALL
25
ALL
0 to 15
26
ALL
OUT_SCALE
27
ALL
0 to 15
28
ALL
OUT_SCALE
29
ALL
0 to 15
30
ALL
OUT_SCALE
31
ALL
0 to 15
32
ALL
OUT_SCALE
33
33.1
RW
33.2
RO
33.3
RO
N/A
33.4
RO
33.5
RO
34
34.1
RW
34.2
RO
34.3
RO
N/A
34.4
RO
34.5
RO
AI Function Block
Initial
Range
Value
Data Type: DS-72
The block alarm is used for all configuration,
hardware, connection failure or system problems
in the block. The cause of the alert is entered in
the subcode field.
Data Type: DS-74
unacknowledged states, unreported states, and
disabled states of the alarms associated with the
function block.
0=clear
0=acknowledged
0=reported
0=enabled
All bits: 0
Data Type: Bit String
0
=
1
All bits: 0
=
Selection of whether alarms associated with the
block will be automatically acknowledged.
Data Type: Float
0.50%
Hysteresis on alarms.
Data Type: Unsigned8
0
The priority of the hi hi alarm.
Data Type: Float
0
Value of analog input which will generate an alarm.
Data Type: Unsigned8
0
The priority of the high alarm.
Data Type: Float
0
Value of analog input which will generate an alarm.
Data Type: Unsigned8
0
The priority of the low alarm.
Data Type: Float
0
Value of analog input which will generate an alarm.
Data Type: Unsigned8
0
The priority of the low low alarm.
Data Type: Float
0
Value of analog input which will generate an alarm.
0
Data Type: DS-71
0
The status of the hi hi alarm and its associated
0
time stamp.
0
0
0
Data Type: DS-71
0
The status of the hi alarm and its associated time
stamp.
0
0
0
−Continued−
Description
Current alert status,
Disable
Enable
4
165
Need help?
Do you have a question about the FIELDVUE DVC6200f and is the answer not in the manual?
Questions and answers