Advertisement

Buffer memory areas related to control methods
The following table shows the buffer memory areas related to each control method.
Buffer memory
name
CH1 Cooling
proportional band (P)
setting, CH1 Heating
proportional band (Ph)
setting (If using normal
mode)
CH1 Cooling
proportional band (Pc)
setting (If using normal
mode)
CH1 Integral time (I)
setting (If using normal
mode)
CH1 Differential time
(D) setting (If using
normal mode)
The temperature control module automatically sets optimum PID constants when the following functions are
used.
• Auto Tuning Function (Page 36 Auto Tuning Function)
• Startup tuning function (Page 41 Startup Tuning Function)
4.4

Manual Control

A manipulated value (MV) can be set manually by users without being automatically calculated using the PID control.
Setting method
Configure the settings as described below.
1.
Set 'CH1 AUTO/MAN mode shift' (Un\G518) to Manual (MAN) (1). (Page 149 CH1 AUTO/MAN mode shift)
2.
Set the manipulated value (MV) in 'CH1 Manual output setting' (Un\G519). (Page 150 CH1 Manual output setting)
Setting range
The settings range is as described below.
• -50 to 1050 (-5.0 to 105.0%)
4 FUNCTION
30
4.4 Manual Control
Buffer memory
Setting range
address
Two-position
control
431
Fix the setting to 0.
439
432
The set value is
ignored.
433
The set value is
ignored.
P control
PD control
0 to 10000 (0.0 to 1000.0% span)
Fix the setting to 0.
Fix the setting to 0.
1 to 3600(s)
P control
PID control
1 to 3600(s)
The set value is
1 to 3600(s)
ignored.