Output
Instead of the transistor output from inside the temperature control module, an analog output value from another analog
module can be used as the manipulated value (MV).
■Setting method
Store the value in 'CH1 Manipulated value (MV) for output with another analog module' (Un\G407) in the buffer memory of
another analog module.
The values that scale the manipulated value (MV) (from the external output range lower limit (Un\G596) to the
external output range upper limit (Un\G595)) are written to the 'CH1 Manipulated value (MV) for output with
another (external) analog module'/'CH1 Manipulated value for heating (MVh) for output with another (external)
analog module' (Un\G407) and 'CH1 Manipulated value for cooling (MVc) for output with another (external)
analog module' (Un\G409), regardless of the control mode switching settings.
4.25

Output Limiter Function

This function sets the upper and lower limit values if outputting the manipulated value (MV) calculated using PID operations to
an external device.
Manipulated value (MV)
100%
Upper limit output limiter
Lower limit output limiter
0%
Setting method
Configure the settings as described below.
[Navigation window]  [Parameter]  Target module  [Module Parameter]  [Application Setting]  [Limiter setting]
Precautions
The output limiter function is disabled during 2-position control implementation.
This range has no control outputs
This range has no control outputs
4 FUNCTION
4.25 Output Limiter Function