Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 103

Temperature control
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Address:
CH
Setting detail
Decimal
Standard PID control
(hexadecimal)
409(199H)
CH1
System area
410(19AH)
CH1
System area
411 to 428
System area
(19BH to 1ACH)
429(1ADH)
CH1
Event
430(1AEH)
CH1
Set value (SV) setting
431(1AFH)
CH1
Proportional band (P) setting
432(1B0H)
CH1
Integral time (I) setting
433(1B1H)
CH1
Differential time (D) setting
434(1B2H)
CH1
Alert set value 1
435(1B3H)
CH1
Alert set value 2
436(1B4H)
CH1
Alert set value 3
437(1B5H)
CH1
Alert set value 4
438(1B6H)
CH1
Temperature process value (PV) for input with another
(external) analog module
439(1B7H)
CH1
System area
440 to 500
System area
(1B8H to 1F4H)
501(1F5H)
CH1
Input range
502, 503
System area
(1F6H, 1F7H)
504(1F8H)
CH1
Control output cycle setting
505(1F9H)
CH1
Control response parameter
506(1FAH)
CH1
Temperature rise completion range setting
507(1FBH)
CH1
Temperature rise completion soak time setting
508(1FCH)
CH1
Upper limit output limiter
509(1FDH)
CH1
Lower limit output limiter
510(1FEH)
CH1
Output change ratio limiter
511(1FFH)
CH1
Upper limit setting limiter
512(200H)
CH1
Lower limit setting limiter
513(201H)
CH1
Setting variation rate limiter
514(202H)
System area
515(203H)
CH1
Normal Operation/Reverse
Operation Setting
516(204H)
CH1
Adjustment sensitivity (dead band) setting
517(205H)
System area
518(206H)
CH1
AUTO/MAN mode shift
519(207H)
CH1
Manual output setting
520(208H)
System area
521(209H)
CH1
System area
522(20AH)
CH1
System area
523(20BH)
CH1
System area
524(20CH)
CH1
System area
525 to 530
System area
(20DH to 212H)
531(213H)
CH1
Alert dead band setting
532(214H)
CH1
Number of alert delay
Default value
Heating/cooling PID
control
Manipulated value for cooling
0
(MVc) for output with another
(external) analog module
Cooling transistor output flag
0
0
0
Heating proportional band
30
(Ph) setting
240
60
0
0
0
0
0
Cooling proportional band
30
(Pc) setting
2
Heating control output cycle
300
setting
0
10
0
Heating upper limit output
1000
limiter
System area
0
System area
0
1300
-100
0
System area
1
10
System area
0
System area
-50
Cooling upper limit output
1000
limiter
Cooling control output cycle
300
setting
Cooling method setting
0
Overlap/dead band setting
0
10
0
Data type
Backup
Monitor
Monitor
Monitor
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
APPX
Appendix 4 Buffer Memory Areas
A
101