Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 146

Temperature control
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
CH Temperature rise completion range setting
Temperature rise completion range setting (If using FX3 allocation mode)
■Setting range
1 to 100 (/ or digit)
■Default value
The default value is 10.
CH1 Temperature rise completion soak time setting
Set the time taken to set 'CH1 Temperature rise judgment flag' (Un\G404) to Within temperature rise completion range (ON)
after the completion of the temperature rise.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
CH Temperature rise completion soak time setting
Temperature rise completion soak time setting (If using FX3 allocation mode)
■Setting range
The setting range is 0 to 3600 (min).
■Default value
The default value is 0 (min).
CH1 Upper limit output limiter
Set the upper limit value for actually outputting the manipulated value (MV) calculated by the standard PID operation to an
external device.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
CH Upper limit output limiter
CH Upper limit output limiter (If using FX3 allocation mode)
■Setting range
The lower limit output limiter +1 to 1050 (105.0% max.).
Set values so that the lower limit output limiter value is smaller than the upper limit output limiter value.
When the lower limit output limiter value is equal to or greater than the upper limit output limiter value, CH Upper/lower limit
output limiter setting error (error code: 1A0H) occurs.
When a value out of the setting value is set, an out of setting range error (error code: 1950H) occurs. When an error has
occurred, the following operations will be executed.
• 'Error flag' (Un\G398, b2) turns ON.
• An error code is stored in 'Latest error code' (Un\G0).
■Two-position control
In the two-position control, this setting is disabled.
■Default value
The default value is 1000 (100.0%).
APPX
144
Appendix 4 Buffer Memory Areas
CH1
CH2
506
706
236
CH1
CH2
507
707
237
CH1
CH2
508
708
64
104
CH3
CH4
906
1106
CH3
CH4
907
1107
CH3
CH4
908
1108
144