SV tracking selection
If turning OFF cascade, this function tracks the slave channel set value in the set values immediately before switching (set
value monitor value).
• 0: SV tracking OFF
• 1: SV tracking ON
If SV tracking is ON
(1)
(1)
Slave channel set value (SV) setting
(2)
Slave channel set value monitor value
(3)
Cascade control ON→OFF switching point
It is possible to prevent sudden changes to the slave channel manipulated value when turning OFF cascade.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
SV tracking selection
SV tracking selection (If using FX3 allocation mode)
■Default value
Set to SV tracking ON (1).
Cascade ON/OFF
Turns ON and OFF cascade during cascade control.
• 0: Cascade OFF
• 1: Cascade ON
During cascade control, auto tuning and startup tuning cannot be implemented.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
Cascade ON/OFF
Cascade ON/OFF (If using FX3 allocation mode)
■Default value
Set to cascade OFF (0).
(2)
t
(3)
If SV tracking is OFF
(1)
CH1
CH2
350
242
CH1
CH2
352
244
Appendix 4 Buffer Memory Areas
(2)
t
(3)
CH3
CH4
351
243
CH3
CH4
353
245
APPX
A
121