CH1 Set value (SV) setting
Sets the PID control and alert process set values.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
CH Set value (SV) setting
CH Set value (SV) setting (If using FX3 allocation mode)
■Setting range
The range is determined by the values set in 'CH1 Upper limit setting limiter' (Un\G511) and 'CH1 Lower limit setting limiter'
(Un\G512). (Page 147 CH1 Upper limit setting limiter, Page 147 CH1 Lower limit setting limiter)
When a value out of the setting range is set in this area, an out of setting range error (error code: 1950H) occurs, and the
status is as described below.
• 'Error flag' (Un\G398, b2) turns ON.
• An error code is stored in 'Latest error code' (Un\G0).
■Setting unit
The value to be set differs depending on the value stored in 'CH1 Decimal point position' (Un\G400). (Page 128 CH1
Decimal point position)
• No decimal point (0): Set a value in increments of 1 ( or digit).
• If there is 1 digit (1) past the decimal point: Set a value (the value multiplied by 10) in increments of 0.1 ().
■Default value
The default value is 0.
CH1 Proportional band (P) setting
Set the proportional band (P) to execute the standard PID control.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
CH Proportional band (P) setting
CH Proportional band (P) setting (If using FX3 allocation mode)
■Setting range
*1
0 to 10000 (span
0.0 to 1000.0%)
*1 During internal temperature inputs, input range span. During internal micro voltage inputs, scaling span. During external inputs, external
input span.
■Two-position control
Set the proportional band (P) to 0.
For details on the two-position control, refer to the following.
Page 26 Control Method
■Default value
The default value is 30 (3.0%).
CH1
CH2
430
630
48
88
CH1
CH2
431
631
58
98
Appendix 4 Buffer Memory Areas
CH3
CH4
830
1030
128
168
CH3
CH4
831
1031
138
178
APPX
135