Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 87

Temperature control
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Auto tuning
Implement auto tuning.
[Tool]  [Module Tool List]
1.
Select "Temperature trace" in "Temperature
Control Module" and click the [OK] button.
2.
Select FX5-4LC, and click the [OK] button.
3.
Select "Monitor data write" from the items
described below.
[Setting]  [Monitor data write]
4.
Set "Setting/Operation mode command" to "1:
Operation mode command".
5.
Set "Auto tuning command" to "1: ON".
6.
Set "Auto tuning command" to "1: ON", "Auto
tuning status" becomes "Implementing" and
the auto tuning starts.
7.
When the auto tuning is completed, "Auto
tuning status" becomes "Stopped".
8.
The temperature control is implemented with
the set PID constants.
8.1 Programming Procedure
8 PROGRAMMING
85
8