If using FX3 allocation mode
The following table describes the list of buffer memory addresses.
■Un\G0 to Un\G4095
Address:
CH
Setting detail
Decimal
Standard PID
(hexadecimal)
control
0(0H)
Flag
1(1H)
CH1
Event
2(2H)
CH2
3(3H)
CH3
4(4H)
CH4
5(5H)
CH1
Measurement value (PV)
6(6H)
CH2
7(7H)
CH3
8(8H)
CH4
9(9H)
CH1
Manipulated value
(control output value)
10(AH)
CH2
(MV) monitor
11(BH)
CH3
12(CH)
CH4
13(DH)
CH1
System area
14(EH)
CH2
15(FH)
CH3
16(10H)
CH4
17(11H)
CH1
Transistor output flag
(Control output flag)
18(12H)
CH2
19(13H)
CH3
20(14H)
CH4
21(15H)
CH1
Heater current process value
22(16H)
CH2
23(17H)
CH3
24(18H)
CH4
25(19H)
CH1
Temperature process value for input with another
(external) analog module
26(1AH)
CH2
27(1BH)
CH3
28(1CH)
CH4
29(1DH)
All
Control start/stop switching
30(1EH)
All
Module information
31(1FH)
All
Firmware version
32(20H)
CH1
Manipulated value
(MV) for output with
33(21H)
CH2
another (external)
34(22H)
CH3
analog module monitor
35(23H)
CH4
36(24H)
CH1
System area
37(25H)
CH2
38(26H)
CH3
39(27H)
CH4
40(28H)
CH1
Set value (SV) monitor
41(29H)
CH2
42(2AH)
CH3
43(2BH)
CH4
Monitor/Settings/
Selection range
Heating/cooling
PID control
Page 123
Page 134
input range span ±5%
Manipulated value for
-5.0 to +105.0%
heating (heating control
output value) (MV)
monitor
Manipulated value for
Normally 0
cooling (MV) monitor
0.0 to 105.0%
-5.0 displayed when control is
stopped
Page 131
0.0 to 105.0 A
-32768 to +32767
0: Control stop
1: Control start
61C2H
1000
Manipulated value
External output range lower
(MVh) for heating for
limit to upper limit
output with another
(external) analog
module monitor
Manipulated value
(MVc) for cooling for
output with another
(external) analog
module monitor
Lower limit setting limiter to
upper limit setting limiter
Default
Data type
Backup
value
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
0
Control
0
Control
61C2H
Monitor
1000
Monitor
0
Monitor
0
Monitor
0
Monitor
APPX
Appendix 4 Buffer Memory Areas
A
109

Advertisement

Table of Contents
loading

Table of Contents