Deviation alert
When the deviation (E) between the temperature process value (PV) and the set value (SV) meets a particular condition, the
system issues the deviation alert.
The set value (SV) that is referenced is the "set value (SV) monitor".
■Setting the set value (SV) and the setting change rate limiter
If the Setting change rate limiter has been set: The "CH1 set value (SV) monitor" (Un\G406) obeys the set value (SV) after the
change as described below.
Temperature process value (PV)
Set value (SV) 2
Change
Set value (SV) 1
0
(1) "Set value (SV) Setting" of "Control basic parameters" in "Application Setting"
(2) 'CH1 Set value (SV) monitor' (Un\G406)
(3) "Setting change rate limiter" of "Limiter setting" in "Application Setting"
■Upper limit deviation alert
When the deviation (E) is equal to or greater than the alert set value, the system issues a deviation alert.
When the alert set value is positive
Temperature process value (PV)
*1
Set value (SV)
Deviation (E) (=Temperature process value (PV) - Set value (SV)
Alert set value
0
Alert status
*1 Depending on the alert mode setting, this value becomes the set value or the monitored value. The setting range of the alert set value is
(-(Full scale of the input range)) to the full scale of the input range. (Page 55 Setting the set value (SV) and the setting change rate
limiter)
(1)
(3)
60 Second
Time
Time
Non-alert status
Alert status
(2)
Time
When the alert set value is negative
Temperature process value (PV)
*1
Set value (SV)
*1
)
Deviation (E) (=Temperature process value (PV) - Set value (SV)
0
Alert set value
Alert status
Time
Time
Non-alert status
Alert status