Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 115

Temperature control
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Address:
CH
Setting detail
Decimal
Standard PID
(hexadecimal)
control
136(88H)
CH3
AT (auto tuning) implementation command
137(89H)
CH3
Operation mode setting
138(8AH)
CH3
Proportional band (P)
setting
139(8BH)
CH3
System area
140(8CH)
CH3
Differential time (I) setting
141(8DH)
CH3
Differential time (D) setting
142(8EH)
CH3
Control response parameter
143(8FH)
CH3
System area
144(90H)
CH3
Upper limit output
limiter
145(91H)
CH3
Lower limit output
limiter
146(92H)
CH3
System area
147(93H)
CH3
Output change ratio
limiter
148(94H)
CH3
Sensor correction value setting
149(95H)
CH3
Controller sensitivity (dead band) setting
150(96H)
CH3
Control output cycle
setting
151(97H)
CH3
System area
152(98H)
CH3
Primary delay digital filter setting
153(99H)
CH3
Setting variation rate limiter
154(9AH)
CH3
AT bias
155(9BH)
CH3
Normal Operation/
Reverse Operation
Setting
156(9CH)
CH3
Upper limit setting limiter
157(9DH)
CH3
Lower limit setting limiter
158(9EH)
CH3
Loop disconnection
detection judgment
time constant
159(9FH)
CH3
Loop disconnection
detection dead band
160(A0H)
CH3
Micro voltage input scaling upper limit
161(A1H)
CH3
Micro voltage input scaling lower limit
162(A2H)
CH3
External input range upper limit
163(A3H)
CH3
External input range lower limit
164(A4H)
CH3
External output range upper limit
Monitor/Settings/
Selection range
Heating/cooling
PID control
0: Stop AT
1: Implement AT
0: Not used
1: Monitor only
2: Monitor + alert
3: Monitor + alert + control
Heating proportional
0 to 10000 (0.1 to 1000.0%
band (P) setting
span)
Set 0 to use position 2
controls.
Cooling proportional
1 to 10000 (0.1 to 1000.0%
band setting
span)
0 to 3600 s
0 to 3600 s
0: Slow
1: Regular
2: Fast
Overlap/dead band
-100 to +100
Heating upper limit
Lower limit output limiter +1 to
output limiter
1050/0 to 1050
System area
-50 to upper limit output limiter
-1
Cooling upper limit
output limiter
System area
0 to 1000
-5000 to +5000
0 to 100
Heating control output
5 to 1000 (0.5 to 100.0s)
cycle setting
Cooling control output
5 to 1000 (0.5 to 100.0s)
cycle setting
0 to 100 s (0: Function OFF)
0 to 1000
±Input span [, , digit]
System area
0: Normal Operation
1: Reverse Operation
Lower limit setting limiter
value +1 to input range upper
limit
Input range lower limit to
Upper limit setting limiter
value -1
System area
0 to 7200 s
System area
0.0 or 0 to input span
-20000 to +20000
(Upper and lower limit reverse
operation disabled, 20000
max. using span)
-32000 to +32000
(Upper and lower limit reverse
operation disabled)
-32000 to +32000
Default
Data type
Backup
value
0
Normal
3
Setting
30
Control
30
Control
240
Control
60
Control
0
Setting
0
Setting
1000
Setting
0
Setting
0
Setting
0
Setting
0
Setting
10
Setting
300
Setting
0/300
Setting
0
Setting
0
Setting
0
Setting
1/0
Setting
1300
Setting
-100
Setting
480/0
Setting
0
Setting
10000
Setting
0
Setting
10000
Setting
0
Setting
10000
Setting
APPX
Appendix 4 Buffer Memory Areas
A
113