Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 112

Temperature control
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Address:
CH
Decimal
(hexadecimal)
44(2CH)
CH1
45(2DH)
CH2
46(2EH)
CH3
47(2FH)
CH4
48(30H)
CH1
49(31H)
CH1
50(32H)
CH1
51(33H)
CH1
52(34H)
CH1
53(35H)
CH1
54(36H)
CH1
55(37H)
CH1
56(38H)
CH1
57(39H)
CH1
58(3AH)
CH1
59(3BH)
CH1
60(3CH)
CH1
61(3DH)
CH1
62(3EH)
CH1
63(3FH)
CH1
64(40H)
CH1
65(41H)
CH1
66(42H)
CH1
67(43H)
CH1
68(44H)
CH1
69(45H)
CH1
70(46H)
CH1
71(47H)
CH1
72(48H)
CH1
73(49H)
CH1
74(4AH)
CH1
75(4BH)
CH1
APPX
110
Appendix 4 Buffer Memory Areas
Setting detail
Standard PID
Heating/cooling
control
PID control
Control mode monitor
Set value (SV) setting
Alert 1 set value
Alert 2 set value
Alert 3 set value
Alert 4 set value
Heater disconnection alert setting
AUTO/MAN mode
System area
switching
Manual output settings
System area
AT (auto tuning) implementation command
Operation mode setting
Proportional band (P)
Heating proportional
setting
band (P) setting
System area
Cooling proportional
band setting
Integral time (I) setting
Differential time (D) setting
Control response parameter
System area
Overlap/dead band
Upper limit output
Heating upper limit
limiter
output limiter
Lower limit output
System area
limiter
System area
Cooling upper limit
output limiter
Output change ratio
System area
limiter
Sensor correction value setting
Controller sensitivity (dead band) setting
Control output cycle
Heating control output
setting
cycle setting
System area
Cooling control output
cycle setting
Primary delay digital filter setting
Setting variation rate limiter
AT bias
Normal Operation/
System area
Reverse Operation
Setting
Monitor/Settings/
Default
Selection range
value
b0 to 2: Control mode
0
b15: Cascade control
implementation status
Within setting limiter range
0
Depends on alert mode and
0
input type
Depends on alert mode and
0
input type
Depends on alert mode and
0
input type
Depends on alert mode and
0
input type
0 to 1000 (0.0 to 100.0 A) (0:
0
Heater disconnection
detection function OFF)
0: AUTO
0
1: MAN
-50 to +1050
-50/0
0: Stop AT
0
1: Implement AT
0: Not used
3
1: Monitor only
2: Monitor + alert
3: Monitor + alert + control
0 to 10000 (0.1 to 1000.0%
30
span)
Set 0 to use position 2
controls.
1 to 10000 (0.1 to 1000.0%
30
span)
0 to 3600s
240
0 to 3600s
60
0: Slow
0
1: Regular
2: Fast
-100 to +100
0
Lower limit output limiter +1 to
1000
1050/0 to 1050
-50 to upper limit output limiter
0
-1
0
0 to 1000
0
-5000 to +5000
0
0 to 100
10
5 to 1000 (0.5 to 100.0s)
300
5 to 1000 (0.5 to 100.0s)
0/300
0 to 100s (0: Function OFF)
0
0 to 1000
0
±Input span [, , digit]
0
0: Normal Operation
1/0
1: Reverse Operation
Data type
Backup
Monitor
Control
Control
Control
Control
Control
Control
Setting
Setting
Normal
Setting
Control
Control
Control
Control
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting