6
WIRING
This section explains the temperature control module wiring.
6.1

Spring Clamp Terminal Block

Suitable wiring
The wires to connect the spring clamp terminal block are described below.
No. of wire per terminal
One wire
Wire end treatment
Strip the cable about 10 mm from the tip to connect a wire ferrule at the striped area. Failure to do so may result in electric
shock or short circuit between adjacent terminals because the conductive part. If the wire strip length is too short, it may result
in the poor contact to the spring clamp terminal part.
Depending on the thickness of the sheath, it may be difficult to insert into the insulation sleeve, so select the wires by referring
to the appearance diagram.
Strand wire/single wire
10 mm
The following table shows wire ferrules and tools for wire ferrules compatible with the terminal block. Use of items other than
these may result in not being able to remove the wire ferrule, so carefully check that the wire ferrule can be unplugged.
<Reference product>
Manufacturer
PHOENIX CONTACT GmbH & Co. KG
6 WIRING
70
6.1 Spring Clamp Terminal Block
Wire size
Single wire, Strand wire
AWG24 to 16
2
(0.2 to 1.5 mm
)
Model
AI 0.5-10 WH
AI 0.75-10 GY
AI 1.0-10
AI 1.5-10
Ferrule with insulation sleeve
AWG23 to 19
(0.25 to 0.75 mm
Ferrule with insulation sleeve
Contact area
Insulation sleeve
(Crimp area)
10 mm
16 to 18 mm
2 to 2.8 mm
Wire size
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
1.5 mm
2
)
Crimp tool
CRIMPFOX 6