11.02
12.95
Rules for the
The following regulations of DIN EN 60086(-4) must be adhered to:
handling of
Backup batteries
backup batteries
S
S
S
S
Rules for handling
The MMC hard disk unit is provided with vibration absorbers. The following rules
MMC 101/102
must nevertheless be followed when handling this unit.
Important
!
Hard disk unit
S
S
S
S
2.2.2

Operating conditions

Relevant
IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-3, EN 60721
standards
Ambient
If the specified values cannot be maintained, a heat exchanger or an air
climatic
conditioning unit must be provided.
conditions
Table 2-9
Temperature range
Permissible change in
relative air humidity
EN 60721-3-3, Class 3K5
Condensation
Temperature variation
Atmospheric pressure
E Siemens AG, 2002. All rights reserved
SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition
2.2 Ambient climatic and mechanical conditions
must not be charged.
must not be heated or thrown into fires.
must not be pierced or squeezed.
must not be tampered with mechanically or electrically in any way!
Transportation in original packaging only
Do not throw the unit or subject it to other shocks
Do not remove the unit from its mechanical assembly
Do not tamper with the springs.
Ambient climatic conditions
See technical data of the relevant component
Within 1 minute
Not allowed
Within 1 minute
When operated at an
altitude 1500m above mean
sea level. For greater
altitudes, the upper limit
temperature must be
reduced by
3.5C/500m.
2 Installation Conditions
max. 0.1%
Max. 0.2K
86kPa to 108kPa