Remote SV input filter constant (Setting range: 0.0 to 900.0 seconds)
[Description]
• This parameter is used to make the input signal fluctua-
tion range smaller (filtering function).
Suppose that the input filter constant is set to 5 seconds.
If the input is suddenly changed from 0 to 100%, the PV
display gradually changes as shown in the figure on the
right, and it takes 5 seconds to change from 0 to 63.2%.
[Note]
• The value is set to 0.0 at the time of delivery (filter OFF).
Do not change the value unless required.
[Setting example] Changing the filter constant from 0.0 (filter OFF) to 5.0 (5 seconds)
Display
1.
2.
3.
4.
5.
6.
1.800.561.8187
76
Press and hold the
key for 5 seconds.
SEL
will be displayed in the PV display section.
Press the
key to display
Press the
SEL
key once.
The current set value (
) in the SV display section flickers.
Press the
and
keys to display
The operation will then be performed with the filter constant of 5.0 seconds.
To display the operation status, press and hold the
www.
Remote SV
input
Input
filter
°C
100
63
(%)
Operating procedure
.
.
SEL
key for 2 seconds.
.com
Y
PID
Control output
Remote SV input
Y
t
5 seconds