[Description]
• This parameter is used for selecting input signals. Input
signal varies depending on the sensors (2 types below).
Set a code that corresponds to the sensor you use.
Type I
Type II
• Input signals can be selected within the same type. It is
impossible to select input signals of a different type.
• For type II, to change from the voltage input to the cur-
rent input, connect the supplied resistance of 250Ω be-
tween terminals !7 and !8 (in the case of PXR4), and
between terminals #5 and #6 (in the case of PXR5/9), in
addition to changing the code.
When changing from the current input to the voltage in-
put, remove the resistance of 250 Ω as well as changing
the code.
[Note]
After changing the codes, power off the PXR, and then
power it on again.
[Setting example] Changing from thermocouple K to thermocouple T in Type I
Display
1.800.561.8187
Input signal code (Setting range: 0 to 16)
: Thermocouples (9 kinds of signals)
Resistance bulbs (1 kind of signal)
: Voltage, current
1.
Press and hold the
will be displayed on the PV display.
2.
Press the
key to display
3.
Press the
key once.
SEL
The current setting ( ) flashes on the SV display.
4.
Press the
or
5.
Press the
SEL
key once.
controller will operate with the kind of input signals being thermocouple T.
6.
If you want to display the operation status, press and hold the
www.
• Input signals and codes
q Input signals code table
Type
I
II
Operating procedure
key for three seconds.
SEL
.
key to display .
will stop flashing and will be registered for
.com
Input signal
Resistance bulb (RTD)
• Pt 100
Thermocouple
• J
• K
• R
• B
• S
• T
• E
• N
• PL-II
1 to 5 V, 4 to 20mA DC
. After that, the
key for two seconds.
SEL
information@itm.com
Code
1
2
3
4
5
6
7
8
12
13
16
39