Proportional Band - FE PXR4 Operation Manual

Micro-controller x
Table of Contents

Advertisement

Proportional band (Setting range: 0.0 to 999.9% of the measured range)
[Description]
• To select the ON/OFF control (two-position control), set
to 0.0. It is not necessary to set
can be automatically set by the auto-tuning operation.
• When
is too small, control will be unstable, and when
is too large, the response will be delayed.
[Setting example] Changing the proportional band from 5.0% to 15.0%
Display
1.
2.
3.
4.
5.
1.800.561.8187
24
and .
Press and hold the
key for three seconds.
SEL
will be displayed on the PV display.
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the
or
keys to display
Press the
key once.
SEL
controller will operate with
If you want to display the operation status, press and hold the
www.
• Set the hysteresis of the ON/OFF control (two-position
control) in the parameter
• If auto-tuning is run after the ON/OFF control is selected,
the ON/OFF control changes to the PID control. To keep
the ON/OFF control selected, do not execute the auto-
tuning.
Operating procedure
.
will stop flashing and will be registered for . After that, the
being 15.0%.
.com
.
SEL
key for two seconds.