Adjusting the PV (Measured value) display (0%) (Setting range: -50 to 50% FS)
Adjusting the PV (Measured value) display (100%) (Setting range: -50 to 50% FS)
[Description]
• The user-definable functions are independent of the adjust-
ment values of the PXR. Setting the parameters of
and
to
can return to the factory default settings.
1.
Prepare the following devices before adjustment by us-
ing these parameters.
• DC voltage standard generator
1 to 5V (for voltage input)
0 to 100 mV (for thermocouple input)
• Decade resistance box
100.0 to 400.0 Ω (for resistance bulb input)
2.
Set the parameter of
3.
Apply a voltage that is equivalent of 0%.
If there is an error large enough to impair its accuracy, set
the parameter of
.)
4.
Apply a voltage that is equivalent of 100%.
If there is an error large enough to impair its accuracy, set
the parameter of
.)
[Setting example] Setting the zero adjustment to "+1°C"
Display
1.
2.
3.
4.
5.
6.
1.800.561.8187
66
to OFF.
. (See the right example to set
. (See the right example to set
Press and hold the
SEL
key for five seconds.
will be displayed on the PV display.
Press the
key to display
Press the
key once.
SEL
The current setting ( ) flashes on the SV display.
Press the
or
keys to display .
Press the
key once.
SEL
controller will operate with the zero adjustment being +1°C.
If you want to display the operation status, press and hold the
www.
5.
Return the parameter of
[Operating example for input range of 0°C to 400°C]
Reading at input of 0°C: -1°C
Reading at input of 400°C: 402°C
Set the parameter of
Set the parameter of
Therefore;
Reading at input of 0°C: 0°C
Reading at input of 400°C: 400°C
[Adjustment example for input range of 0 to 400°C]
Before adjustment
Display at input of 0°C: -1°C
Display at input of 400°C: 402°C
Setting the parameters of
turns to the factory default settings.
Operating procedure
.
will stop flashing and will be registered for
.com
to ON.
to "1".
to "-2".
Adjustment value
After adjustment
: 1
Display at input of 0°C: 0°C
: -2
Display at input of 400°C: 400°C
and
to "0" re-
. After that, the
key for two seconds.
SEL
information@itm.com