Re-transmission base scale (Setting range: -100.0 to 100.0%) (Option)
Re-transmission span scale (Setting range: -100.0 to 100.0%) (Option)
[Description]
• The retransmission base scale and span scale can be set
as shown below. Unit for the setting is %.
Output type
PV/SV/DV
MV
Note 1: Calculate the set value by using the following for-
mula (refer also to the setting example shown below).
Set value (%) = (A ÷ B) × 100 [%]
A = Temperature to be set – Set value of parameter "P-SL"
B = Set value of parameter "P-SU" – Set value of "P-SL"
[Setting example] At K thermocouple input of 0 to 400˚C, make the setting so that the PV (value of
Since the measurement range is 0 to 400˚C, P – SL = 0 (lower limit value of measurement range), and P – SU = 400 (upper
limit value of measurement range). So, from the formula shown above,
A = (100˚C – 0) or (300˚C – 0), B = 400 – 0 = 400
1) Setting Ao-L : What position is 100˚C in the temperature range from 0 to 400˚C ? = 25% (=(100 – 0) ÷ 400 × 100 [%]) → Ao-L = 25.0 (%)
2) Setting Ao-H : What position is 300˚C in the temperature range from 0 to 400˚C ? = 75% (=(300 – 0) ÷ 400 × 100 [%]) → Ao-H = 75.0 (%)
Display
1.
PV indication
2.
3.
4.
5.
6.
7.
8.
9.
10.
SV indication
PV indication
1.800.561.8187
74
Description of percentage
Percentage of input measurement
range (Note 1)
Output value
retransmission output type) becomes 0% at 100˚C, and 100% at 300˚C.
SEL
Press and hold the
for five seconds.
will be displayed.
Press the
key to display
SEL
Press the
key once. The current setting value will be displayed.
Press the
or
key to flicker and to display
Press the
SEL
key once.
(Repeat the procedure from 3 to 5 to check the set value.)
Press the
key to display
SEL
Press the
key once. The current setting value will be displayed.
Press the
or
key to flicker and to display
Press the
SEL
key once.
(Repeat the procedure from 7 to 9 to check the set value.)
If you want to display the operation status, press and hold the
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
www.
• When the value of retransmission output (example: SV)
becomes equal to the set value of Ao-L, the retransmis-
sion output becomes 0% (output).
• When the value of retransmission output (example: PV)
becomes equal to the set value of Ao-H, the retransmis-
sion output becomes 100% (output).
Related parameters:
[Note]
• Be sure to always set
Operating procedure
.
.
will be displayed and
will be registered for the retransmission base scale.
.
.
will be displayed and
will be registered for the retransmission span scale.