5.7 INPUTS/OUTPUTS
c) REMOTE DEVICES: DEVICE ID FOR RECEIVING GSSE MESSAGES
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE DEVICE
Sixteen remote devices, numbered from 1 to 16, can be selected for setting purposes. A receiving relay must be pro-
grammed to capture messages from only those originating remote devices of interest. This setting is used to select specific
remote devices by entering (bottom row) the exact identification (ID) assigned to those devices.
The
REMOTE DEVICE 1(16) VLAN ID
they are not applicable to GSSE messages. The
remote device is sending the GOOSE message. The
cation identification in the GOOSE message. These settings should match the corresponding settings on the sending
device.
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE INPUT 1
5
Remote Inputs which create FlexLogic™ operands at the receiving relay, are extracted from GSSE/GOOSE messages
originating in remote devices. The relay provides 32 remote inputs, each of which can be selected from a list consisting of
64 selections: DNA-1 through DNA-32 and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC
61850 specification and is presented in the IEC 61850 DNA Assignments table in the Remote Outputs section. The function
of UserSt inputs is defined by the user selection of the FlexLogic™ operand whose state is represented in the GSSE/
GOOSE message. A user must program a DNA point from the appropriate FlexLogic™ operand.
Remote Input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The
REMOTE INPUT 1 ID
selects the number (1 to 16) of the remote device which originates the required signal, as previously assigned to the remote
device via the setting
REMOTE DEVICE NN ID
of the GSSE/GOOSE message required.
The
REMOTE IN 1 DEFAULT STATE
the remote device sending the point is declared to be non-communicating. The following choices are available:
Setting
REMOTE IN 1 DEFAULT STATE
Setting
REMOTE IN 1 DEFAULT STATE
5-210
REMOTE DEVICES
1
REMOTE DEVICE
Remote Device 1
REMOTE DEVICE
MESSAGE
VLAN ID: 0
REMOTE DEVICE
MESSAGE
ETYPE APPID: 0
and
REMOTE DEVICE 1(16) ETYPE APPID
REMOTE DEVICE 1(16) VLAN ID

REMOTE INPUTS

REMOTE INPUT
Remote Ip
REMOTE IN
MESSAGE
Remote Device
REMOTE IN
MESSAGE
PAIR: None
REMOTE IN
MESSAGE
STATE: Off
REMOTE IN
MESSAGE
EVENTS: Disabled
setting allows the user to assign descriptive text to the remote input. The
(see the Remote Devices section).
setting selects the logic state for this point if the local relay has just completed startup or
to "On" value defaults the input to Logic 1.
to "Off" value defaults the input to Logic 0.
L60 Line Phase Comparison Relay
REMOTE DEVICE 1(16)
Range: up to 20 alphanumeric characters
1 ID:
Range: 0 to 4095 in steps of 1
1
Range: 0 to 16383 in steps of 1
1
settings are only used with GOOSE messages;
setting identifies the virtual LAN on which the
REMOTE DEVICE 1(16) ETYPE APPID
REMOTE INPUT 1(32)
Range: up to 12 alphanumeric characters
1 ID:
1
Range: 1 to 16 inclusive
1 DEVICE:
1
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32
1 BIT
Range: On, Off, Latest/On, Latest/Off
1 DEFAULT
Range: Disabled, Enabled
1
REMOTE IN 1 BIT PAIR
5 SETTINGS
setting identifies the Ethernet appli-
5.7.6 REMOTE INPUTS
setting
REMOTE IN 1 DEVICE
selects the specific bits