5 SETTINGS
SETTING
BREAKER 1 ARCING
AND
AMP FUNCTION:
Disabled=0
Enabled=1
SETTING
OR
BREAKER 1 ARCING
AMP BLOCK:
Off=0
AND
SETTINGS
BREAKER 1 ARCING
AMP INIT-A:
Off=0
BREAKER 1 ARCING
AMP INIT-B:
Off=0
OR
BREAKER 1 ARCING
AMP INIT-C:
Off=0
SETTING
BREAKER 1 ARCING
AMP SOURCE:
IA
IB
IC
COMMAND
CLEAR BREAKER 1
ARCING AMPS:
NO=0
YES=1
Figure 5–105: BREAKER ARCING CURRENT SCHEME LOGIC
c) BREAKER FLASHOVER
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER
FLASHOVER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
SETTING
BREAKER 1 ARCING
AMP DELAY:
100 ms
0
0
AND
RUN
Integrate
AND
RUN
Integrate
AND
RUN
Integrate
MONITORING ELEMENTS
BKR 1 FLSHOVR
FUNCTION: Disabled
BKR 1 FLSHOVR SIDE 1
SRC: SRC 1
BKR 1 FLSHOVR SIDE 2
SRC: None
BKR 1 STATUS CLSD A:
Off
BKR 1 STATUS CLSD B:
Off
BKR 1 STATUS CLSD C:
Off
BKR 1 FLSHOVR V PKP:
0.850 pu
BKR 1 FLSHOVR DIFF V
PKP: 1000 V
BKR 1 FLSHOVR AMP
PKP: 0.600 pu
BKR 1 FLSHOVR PKP
DELAY: 0.100 s
BKR 1 FLSHOVR SPV A:
Off
L60 Line Phase Comparison Relay
Add to
Accumulator
IA -Cycle
2
Select
2
IB -Cycle
Highest
Value
IC -Cycle
2
ACTUAL VALUE
Set All To Zero
BKR 1 ARCING AMP A
BKR 1 ARCING AMP B
BKR 1 ARCING AMP C
BKR 1 OPERATING TIME A
BKR 1 OPERATING TIME B
BKR 1 OPERATING TIME C
BKR 1 OPERATING TIME
BREAKER FLASHOVER 1(2)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 1.500 pu in steps of 0.001
Range: 0 to 100000 V in steps of 1
Range: 0.000 to 1.500 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
5.6 CONTROL ELEMENTS
SETTING
BREAKER 1 ARCING
AMP LIMIT:
FLEXLOGIC OPERANDS
2
KA Cycle Limit
BKR1 ARC OP
*
BKR1 ARC DPO
Φ
Φ
Φ
827071A3.CDR
Φ
Φ
Φ
5-179
5