2.2 SPECIFICATIONS

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated Form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
NOTE
2
interfacing with other IEDs or power system devices via communications or different output contacts.
87PC SCHEME
Signal selection:
Fault detector low:
Fault detector high:
Signal symmetry
adjustment:
Channel delay
adjustment:
Channel adjustments:
Operate time (typical):
PHASE DISTANCE
Characteristic:
Number of zones:
Directionality:
Reach (secondary Ω):
Reach accuracy:
Distance:
Characteristic angle:
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
Limit angle:
Right blinder (Quad only):
Reach:
Characteristic angle:
Left Blinder (Quad only):
Reach:
Characteristic angle:
Time delay:
Timing accuracy:
Current supervision:
Level:
Pickup:
Dropout:
Memory duration:
VT location:
CT location:
Voltage supervision pickup (series compensation applications):
Operation time:
Reset time:
2-8
Mixed I_2 - K*I_1 (K = 0.00 to 0.25 in
steps of 0.01), or 3I_0
0.02 to 15.00 pu in steps of 0.01
0.1 to 15.0 pu in steps of 0.1
–5.0 to 5.0 ms in steps of 0.1
0.000 to 30.00 ms in steps of 0.001
Channel delay and signal symmetry
compensation
3/4 cycle for single phase comparison
1/2 cycle for dual phase comparison
Mho (memory polarized or offset) or
Quad (memory polarized or non-direc-
tional)
3
forward, reverse, or non-directional
0.02 to 500.00 Ω in steps of 0.01
±5% including the effect of CVT tran-
sients up to an SIR of 30
30 to 90° in steps of 1
30 to 90° in steps of 1
30 to 90° in steps of 1
0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.000 to 65.535 s in steps of 0.001
±3% or 4 ms, whichever is greater
line-to-line current
0.050 to 30.000 pu in steps of 0.001
97 to 98%
5 to 25 cycles in steps of 1
all delta-wye and wye-delta transformers
all delta-wye and wye-delta transformers
0 to 5.000 pu in steps of 0.001
1 to 1.5 cycles (typical)
1 power cycle (typical)
L60 Line Phase Comparison Relay
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

GROUND DISTANCE
Characteristic:
Mho (memory polarized or offset) or
Quad (memory polarized or non-direc-
tional)
Reactance polarization: negative-sequence or zero-sequence
current
Non-homogeneity angle: –40 to 40° in steps of 1
Number of zones:
3
Directionality:
forward, reverse, or non-directional
Reach (secondary Ω):
0.02 to 500.00 Ω in steps of 0.01
Reach accuracy:
±5% including the effect of CVT tran-
sients up to an SIR of 30
Distance characteristic angle: 30 to 90° in steps of 1
Distance comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Zero-sequence compensation
Z0/Z1 magnitude:
0.00 to 10.00 in steps of 0.01
Z0/Z1 angle:
–90 to 90° in steps of 1
Zero-sequence mutual compensation
Z0M/Z1 magnitude:
0.00 to 7.00 in steps of 0.01
Z0M/Z1 angle:
–90 to 90° in steps of 1
Right blinder (Quad only):
Reach:
0.02 to 500 Ω in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Left blinder (Quad only):
0.02 to 500 Ω in steps of 0.01
Reach:
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
Current supervision:
Level:
neutral current (3I_0)
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
LINE PICKUP
Phase IOC:
0.000 to 30.000 pu
Undervoltage pickup:
0.000 to 3.000 pu
Overvoltage delay:
0.000 to 65.535 s