GE L60 Instruction Manual page 171

Ur series line phase comparison relay
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
b) 87PC SCHEME
PATH: SETTINGS
GROUPED ELEMENTS
87PC SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
PHASE COMPARISON ELEMENTS
87PC FUNCTION:
Disabled
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
87PC BLOCK:
Off
87PC SIGNAL SOURCE:
One Source Current
87PC SIGNAL:
Mixed I_2-K*I_1
87PC MIXED SIGNAL K:
0.20
87PC FDL PICKUP:
0.50 pu
87PC FDL AUX:
Off
87PC FDH PICKUP:
0.75 pu
87PC FDH AUX:
Off
87PC CH1 ASYMMETRY:
0.0 ms
87PC CH2 ASYMMETRY:
0.0 ms
87PC CH1 DELAY:
0.0 ms
87PC CH2 DELAY:
0.0 ms
87PC CH1 RX VOLT:
12.0 V
87PC CH2 RX VOLT:
12.0 V
87PC STABILITY
ANGLE:
75°
87PC RESET DELAY:
30 ms
87PC TRANS BLOCK
PICKUP: 0.030 s
87PC TRANS BLOCK
RESET: 0.030 s
87PC CHNL LOSS TRIP
WINDOW:
0 msec
L60 Line Phase Comparison Relay
5.5 GROUPED ELEMENTS
87PC SCHEME
Range: Disabled, Enabled
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
Range: FlexLogic™ operand
Range: One Source Current, Two Sources Current
Range: Mixed I_2–K*I_1, 3I_0
Range: 0.00 to 0.25 in steps of 0.01
Range: 0.02 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: 0.01 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: –5.0 to 5.0 ms in steps of 0.1
Range: –5.0 to 5.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: 0.0 to 125.0 V in steps of 0.1
Range: 40 to 140° in steps of 5
Range: 0 to 200 ms in steps of 1
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 500 ms in steps of 1