GE L60 Instruction Manual page 446

Ur series line phase comparison relay
Hide thumbs Also See for L60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
bitmask
element
730
Digital Element 39
731
Digital Element 40
732
Digital Element 41
733
Digital Element 42
734
Digital Element 43
735
Digital Element 44
B
736
Digital Element 45
737
Digital Element 46
738
Digital Element 47
739
Digital Element 48
F125
ENUMERATION: ACCESS LEVEL
0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service
F126
ENUMERATION: NO/YES CHOICE
0 = No, 1 = Yes
F127
ENUMERATION: LATCHED OR SELF-RESETTING
0 = Latched, 1 = Self-Reset
F128
ENUMERATION: CONTACT INPUT THRESHOLD
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
F129
ENUMERATION: FLEXLOGIC TIMER TYPE
0 = millisecond, 1 = second, 2 = minute
F130
ENUMERATION: SIMULATION MODE
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
B-60
F135
ENUMERATION: GAIN CALIBRATION
0 = 0x1, 1 = 1x16
F136
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles
3 = 3 x 64 cycles, 4 = 1 x 128 cycles
F138
ENUMERATION: OSCILLOGRAPHY FILE TYPE
0 = Data File, 1 = Configuration File, 2 = Header File
F140
ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE,
DISABLED
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V,
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A,
6 = Notched 2 A
F141
ENUMERATION: SELF TEST ERROR
bitmask
0
1
2
4
5
9
10
11
13
14
15
18
19
20
21
22
23
24
25
26
27
30
31
F142
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE
0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
L60 Line Phase Comparison Relay
error
Any Self Tests
IRIG-B Failure
DSP Error
No DSP Interrupts
Unit Not Calibrated
Prototype Firmware
Flexlogic Error Token
Equipment Mismatch
Unit Not Programmed
System Exception
Latching Out Error
SNTP Failure
Battery Failure
Primary Ethernet Failure
Secondary Ethernet Failure
EEPROM Data Error
SRAM Data Error
Program Memory
Watchdog Error
Low On Memory
Remote Device Off
Any Minor Error
Any Major Error
APPENDIX B
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents