2 PRODUCT DESCRIPTION
CONTROL POWER EXTERNAL OUTPUT
(FOR DRY CONTACT INPUT)
Capacity:
100 mA DC at 48 V DC
Isolation:
±300 Vpk
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
Standard output points: 32
User output points:
32
RS232
Front port:
19.2 kbps, Modbus
RS485
1 or 2 rear ports:
Up to 115 kbps, Modbus
together at 36 Vpk
Typical distance:
1200 m
Isolation:
2 kV
GE Multilin
DCMA OUTPUTS
Range:
Max. load resistance:
Accuracy:
99% Settling time to a step change: 100 ms
Isolation:
Driving signal:
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
ETHERNET (FIBER)
®
RTU
PARAMETER
®
RTU, isolated
Wavelength
Connector
Transmit power
Receiver sensitivity
Power budget
Maximum input
power
Typical distance
Duplex
Redundancy
ETHERNET (COPPER)
Modes:
Connector:
SNTP clock synchronization error: <10 ms (typical)
L60 Line Phase Comparison Relay
2.2 SPECIFICATIONS
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
1.5 kV
any FlexAnalog quantity
0.001

2.2.8 COMMUNICATIONS

FIBER TYPE
10MB MULTI-
100MB MULTI-
100MB SINGLE-
MODE
MODE
820 nm
1310 nm
ST
ST
–20 dBm
–20 dBm
–30 dBm
–30 dBm
10 dB
10 dB
–7.6 dBm
–14 dBm
1.65 km
2 km
full/half
full/half
yes
yes
10 MB, 10/100 MB (auto-detect)
RJ45
2
MODE
1310 nm
SC
–15 dBm
–30 dBm
15 dB
–7 dBm
15 km
full/half
yes
2-15