GE L60 Instruction Manual page 413

Ur series line phase comparison relay
Hide thumbs Also See for L60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 47)
ADDR
REGISTER NAME
6307
Negative Sequence Time Overcurrent 1 Target
6308
Negative Sequence Time Overcurrent 1 Events
6309
Reserved (7 items)
6310
...Repeated for Negative Sequence Time Overcurrent 2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
6400
Negative Sequence Instantaneous OC 1 Function
6401
Negative Sequence Instantaneous OC 1 Signal Source
6402
Negative Sequence Instantaneous Overcurrent 1 Pickup
6403
Negative Sequence Instantaneous Overcurrent 1 Delay
6404
Negative Sequence Instantaneous OC 1 Reset Delay
6405
Negative Sequence Instantaneous Overcurrent 1 Block
6406
Negative Sequence Instantaneous Overcurrent 1 Target
6407
Negative Sequence Instantaneous Overcurrent 1 Events
6408
Reserved (8 items)
6410
...Repeated for Negative Sequence Instantaneous OC 2
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
65CE
Power Swing Detect Delay 3 Pickup
65CF
Power Swing Detect Delay 4 Pickup
65D0
Power Swing Detect Seal In Delay
65D1
Power Swing Detect Trip Mode
65D2
Power Swing Detect Block
65D3
Power Swing Detect Target
65D4
Power Swing Detect Event
65D5
Power Swing Detect Shape
65D6
Power Swing Detect Quad Forward Middle
65D7
Power Swing Detect Quad Forward Outer
65D8
Power Swing Detect Quad Reverse Middle
65D9
Power Swing Detect Quad Reverse Outer
65DA
Power Swing Detect Outer Right Blinder
65DB
Power Swing Detect Outer Left Blinder
65DC
Power Swing Detect Middle Right Blinder
65DD
Power Swing Detect Middle Left Blinder
65DE
Power Swing Detect Inner Right Blinder
65DF
Power Swing Detect Inner Left Blinder
Load Encroachment (Read/Write Grouped Setting)
6700
Load Encroachment Function
6701
Load Encroachment Source
6702
Load Encroachment Minimum Voltage
6703
Load Encroachment Reach
6704
Load Encroachment Angle
GE Multilin
RANGE
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0 to 1
0 to 5
0 to 3
0.02 to 250
5 to 50
L60 Line Phase Comparison Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F514
---
1
F300
---
1
F109
---
1
F102
---
1
F085
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
---
1
F102
---
1
F167
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
DEFAULT
0 (Self-reset)
0 (Disabled)
0
B
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
30
50
17
9
17
400
0 (Delayed)
0
0 (Self-reset)
0 (Disabled)
0 (Mho Shape)
6000
7000
6000
7000
10000
10000
10000
10000
10000
10000
0 (Disabled)
0 (SRC 1)
250
100
30
B-27