5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
DNP NETWORK
CLIENT ADDRESSES
The
DNP UNSOL RESPONSE FUNCTION
mechanism. The
DNP UNSOL RESPONSE TIMEOUT
response. The
DNP UNSOL RESPONSE MAX RETRIES
ited response without receiving confirmation from the master; a value of "255" allows infinite re-tries. The
RESPONSE DEST ADDRESS
ited responses are sent is determined by the L60 from the current TCP connection or the most recent UDP message.
The
DNP SCALE FACTOR
log Input data into types: current, voltage, power, energy, and other. Each setting represents the scale factor for all Analog
Input points of that type. For example, if the
Input points that are voltages will be returned with values 1000 times smaller (e.g. a value of 72000 V on the L60 will be
5
returned as 72). These settings are useful when analog input values must be adjusted to fit within certain ranges in DNP
masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (i.e. the value will be 10 times larger).
The
DNP DEFAULT DEADBAND
settings group the L60 Analog Input data into types: current, voltage, power, energy, and other. Each setting represents the
default deadband value for all Analog Input points of that type. For example, to trigger unsolicited responses from the L60
when any current values change by 15 A, the
these settings are the deadband default values. DNP Object 34 points can be used to change deadband values, from the
default, for each individual DNP Analog Input point. Whenever power is removed and re-applied to the L60, the default
deadbands will be in effect.
The L60 relay does not support energy metering. As such, the
DEFAULT DEADBAND
NOTE
The
DNP TIME SYNC IIN PERIOD
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The
DNP MESSAGE FRAGMENT SIZE
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the "DNP Points Lists" L60 web page to view the points lists. This page can be viewed with a web
browser by entering the L60 IP address to access the L60 "Main Menu", then by selecting the "Device Infor-
NOTE
mation Menu" > "DNP Points Lists" menu item.
The
DNP OBJECT N DEFAULT VARIATION
2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation 0 is requested and/or in
class 0, 1, 2, or 3 scans. Refer to the DNP Implementation section in Appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the L60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The L60 can be configured to sup-
5-16
COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
MESSAGE
0.0.0.0
CLIENT ADDRESS 3:
MESSAGE
0.0.0.0
CLIENT ADDRESS 4:
MESSAGE
0.0.0.0
CLIENT ADDRESS 5:
MESSAGE
0.0.0.0
should be "Disabled" for RS485 applications since there is no collision avoidance
sets the time the L60 waits for a DNP master to confirm an unsolicited
setting determines the number of times the L60 retransmits an unsolic-
is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
settings are numbers used to scale Analog Input point values. These settings group the L60 Ana-
DNP VOLTAGE SCALE FACTOR
settings determine when to trigger unsolicited responses containing Analog Input data. These
DNP CURRENT DEFAULT DEADBAND
settings are not applicable.
setting determines how often the Need Time Internal Indication (IIN) bit is set by the L60.
setting determines the size, in bytes, at which message fragmentation occurs. Large
settings allow the user to select the DNP default variation number for object types 1,
L60 Line Phase Comparison Relay
DNP PROTOCOL
DNP NETWORK CLIENT ADDRESSES
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
setting is set to a value of 1000, all DNP Analog
setting should be set to "15". Note that
DNP ENERGY SCALE FACTOR