5.5 GROUPED ELEMENTS
5
Figure 5–47: APPLICATIONS OF THE
PHS DIST Z1 REACH: This setting defines the zone reach for the forward and reverse applications. In the non-direc-
tional applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-directional
applications is set independently. The reach impedance is entered in secondary ohms. The reach impedance angle is
entered as the
PHS DIST Z1 RCA
PHS DIST Z1 RCA: This setting specifies the characteristic angle (similar to the 'maximum torque angle' in previous
technologies) of the phase distance characteristic for the forward and reverse applications. In the non-directional appli-
cations, this setting defines the angle of the forward reach impedance. The reverse reach impedance in the non-direc-
tional applications is set independently. The setting is an angle of reach impedance as shown in Mho and Quadrilateral
Distance Characteristic figures. This setting is independent from
extra directional supervising function.
PHS DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
"Forward" or "Reverse".
PHS DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (
PHS DIST Z1 DIR
"Reverse".
PHS DIST Z1 COMP LIMIT: This setting shapes the operating characteristic. In particular, it produces the lens-type
characteristic of the mho function and a tent-shaped characteristic of the reactance boundary of the quadrilateral func-
tion. If the mho shape is selected, the same limit angle applies to both the mho and supervising reactance compara-
tors. In conjunction with the mho shape selection, the setting improves loadability of the protected line. In conjunction
with the quadrilateral characteristic, this setting improves security for faults close to the reach point by adjusting the
reactance boundary into a tent-shape.
PHS DIST Z1 DIR RCA: This setting selects the characteristic angle (or 'maximum torque angle') of the directional
supervising function. If the mho shape is applied, the directional function is an extra supervising function as the
dynamic mho characteristic is itself directional. In conjunction with the quadrilateral shape, this setting defines the only
5-94
(a)
o
delta
wye, 330
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = None
Z1
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = Dy11
(c)
o
delta
wye, 330
Z3
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1
Z1
Z1 XFRM VOL CONNECTION = Dy11
Z1 XFRM CUR CONNECTION = None
setting.
setting). This setting does not apply when the zone direction is set to "Forward" or
L60 Line Phase Comparison Relay
(b)
lag
delta
Z3
Z3 XFRM VOL CONNECTION = Yd1
Z3 XFRM CUR CONNECTION = None
Z1 XFRM VOL CONNECTION = None
Z1 XFRM CUR CONNECTION = Dy11
(e)
lag
L
1
Zone 3
Z
L1
PH DIST XFMR VOL/CUR CONNECTION
PHS DIST Z1 DIR RCA
5 SETTINGS
o
wye, 330
lag
Z1
L
2
Zone 1
Z
Z
T
L2
830717A1.CDR
SETTINGS
, the characteristic angle of an
PHS DIST Z1 DIR
GE Multilin