Advertisement

5.2 PRODUCT SETUP
Table 5–4: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
LED 1 Operand
LED 2 Operand
LED 3 Operand
LED 4 Operand
LED 5 Operand
LED 6 Operand
LED 7 Operand
LED 8 Operand
LED 9 Operand
LED 10 Operand
LED 11 Operand
LED 12 Operand
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
5
SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
messages. Moreover, they will not trigger the
minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter
7 for additional information on major and minor self-test alarms.
5-30
PARAMETER
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off

USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
MESSAGE
FUNCTION: Enabled
REMOTE DEVICE OFF
MESSAGE
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ANY MINOR ALARM
L60 Line Phase Comparison Relay
SETTING
PARAMETER
LED 13 Operand
Off
LED 14 Operand
BREAKER 2 OPEN
LED 15 Operand
BREAKER 2 CLOSED
LED 16 Operand
BREAKER 2 TROUBLE
LED 17 Operand
SYNC 1 SYNC OP
LED 18 Operand
SYNC 2 SYNC OP
LED 19 Operand
Off
LED 20 Operand
Off
LED 21 Operand
AR ENABLED
LED 22 Operand
AR DISABLED
LED 23 Operand
AR RIP
LED 24 Operand
AR LO
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
or
messages. When in the "Enabled" mode,
ANY SELF-TEST
5 SETTINGS
GE Multilin