Emerson Powerdrive F300 Reference Manual page 89

Hide thumbs Also See for Powerdrive F300:

Advertisement

Value
Text
0
Set
1
Powered
2
Running
3
Acc Powered
4
Local Keypad
5
Remote Keypad
6
Slot 1
7
Slot 2
8
Slot 3
9
Slot 4
Date/Time Selector (06.019) is used to select the drive date and time as shown in the table below.
Date/Time Selector
Date/Time Source
(06.019)
0: Set
Date and time parameters can be written by the user.
1: Power
Time since the drive was powered up.
2: Running
Accumulated drive running time since the drive was manufactured.
3: Acc Power
Accumulated powered-up time since the drive was manufactured.
If a keypad fitted to the front of the drive includes a real-time clock then the date/time from
4: Local Keypad
this clock is displayed, otherwise the date/time is set to zero.
If a keypad connected to the user comms port of a drive with a 485 includes a real-time
5: Remote Keypad
clock then the date/time from this clock is displayed, otherwise the date/time is set to zero.
6: Slot 1
As 4 above, but for option slot 1
7: Slot 2
As 4 above, but for option slot 2
8: Slot 3
As 4 above, but for option slot 3
9: Slot 4
As 4 above, but for option slot 4
When Date/Time Selector (06.019) = 0 the Date (06.016) and Time (06.017) can be written by the user and the values in these parameters are
transferred to the real time clocks in the keypad or any option modules that support this feature that are fitted to the drive. When Date/Time Selector
(06.019) is changed to any other value, the real time clocks are allowed to run normally again. When Date/Time Selector (06.019) is changed from any
value to 0 the date and time from a real time clock, if present, is automatically loaded into Date (06.016) and Time (06.017), so that this date and time is
used as the initial value for editing. If more than one real time clock is present the date/time from the keypad is used, if present, and if not then the
date/time from the lowest number slot with a real time clock is used.
Date (06.016) and Time (06.017) are used by the timers in Menu 09 and for time stamping trips. These features will continue to use the originally selected
clock even if Date/Time Selector (06.019) is changed until a drive reset is initiated. If Date/Time Selector (06.019) has been changed and a reset is
initiated Timer 1 Repeat Function (09.039) and Timer 2 Repeat Function (09.049) are set to zero to disable the timers, and the trip dates and times
(10.041 to 10.060) are reset to zero.
Parameter
06.020 Date Format
Short description
Defines if the US date format is used or not
Mode
Open‑Loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
Std
1
US
Date Format (06.020) selects the display style for Date (06.016), Timer 1 Start Date (09.035), Timer 1 Stop Date (09.037), Timer 2 Start Date (09.045),
Timer 2 Stop Date (09.047), and for the trip time stamping date parameters (10.041, 10.043, 10.045, 10.047, 10.049, 10.051, 10.053, 10.055,
10.057 and 10.059) when displayed on a keypad connected to the drive. The format selection made in this parameter does not affect the value of these
parameters if they are read using comms or by an applications program.
If Date Format (06.020) is 0 then standard format is used and the date is displayed on the keypad as dd.mm.yy and if Date Format (06.020) is 1 then US
format is used and the date is displayed on the keypad as mm.dd.yy.
Parameter
06.021 Time Between Filter Changes
Short description
Defines the time between filter changes
Mode
Open‑Loop
Minimum
0
Default
0
Type
16 Bit User Save
Display Format
Standard
Coding
RW
Time Between Filter Changes (06.021) should be set to a non-zero value to enable the filter change timer system. Each time
Filter Change Required / Change Done (06.022) is changed by the user from 1 to 0 the value of Time Between Filter Changes (06.021) is copied to
Time Before Filter Change Due (06.023). For each hour while Drive Active (10.002) = 1 the Time Before Filter Change Due (06.023) is reduced by 1 until
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
30000
Units
Hours
Update Rate
Background read
Decimal Places
0
89