Parameter
01.002 Pre-skip Filter Reference
Short description
Displays the level of the reference after the reference clamps
Mode
Open‑Loop
Minimum
−VM_SPEED_FREQ_REF
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, VM, ND, NC, PT
Pre-skip Filter Reference (01.002) is the level of the reference after the reference clamps but before the skip filters.
Parameter
01.003 Pre-ramp Reference
Short description
Displays the final output from the Menu 1 reference system
Mode
Open‑Loop
Minimum
−VM_SPEED_FREQ_REF
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, VM, ND, NC, PT
The Pre-ramp Reference (01.003) is the final output from the Menu 1 reference system that is fed into the Menu 2 ramp system.
Parameter
01.004 Reference Offset
Short description
Defines the the offset applied to the reference
Mode
Open‑Loop
Minimum
−VM_SPEED_FREQ_REF
Default
0.0
Type
32 Bit User Save
Display Format
Standard
Coding
RW, VM
If Reference Offset Select (01.009) = 0 then Reference Selected (01.001) is the selected reference multiplied by [1 + (Percentage Trim (01.038) / 100.00)].
If Reference Offset Select (01.009) = 1 then the Reference Offset (01.004) is added to the selected reference to give Reference Selected (01.001).
Parameter
01.006 Maximum Reference Clamp
Short description
Defines the maximum value for the reference
Mode
Open‑Loop
Minimum
−VM_POSITIVE_REF_CLAMP1
Default
See exceptions below
Type
32 Bit User Save
Display Format
Standard
Coding
RW, VM
Region
Default Value
50Hz
50.0
60Hz
60.0
Maximum Reference Clamp (01.006) provides a limit on the maximum frequency or speed. (If Select Motor 2 Parameters (11.045) = 1 then
M2 Maximum Reference Clamp (21.001) is used instead.)
Parameter
01.007 Minimum Reference Clamp
Short description
Defines the minimum value for the reference
Mode
Open‑Loop
Minimum
−VM_NEGATIVE_REF_CLAMP1
Default
0.0
Type
32 Bit User Save
Display Format
Standard
Coding
RW, VM
If Negative Reference Clamp Enable (01.008) = 1 then Minimum Reference Clamp (01.007) is forced to be a negative value and is applied to the final
reference as the negative limit. If Negative Reference Clamp Enable (01.008) = 0 then -Maximum Reference Clamp (01.006) is applied to the final
reference as the negative limit. (If Select Motor 2 Parameters (11.045) = 1 then M2 Minimum Reference Clamp (21.002) is used instead.)
The minimum reference clamp is also used to provide the minimum speed limit for uni-polar mode (i.e. Bipolar Reference Enable (01.010) = 0) after
the Reference Selected (01.001).
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Maximum
VM_SPEED_FREQ_REF
Units
Update Rate
4ms write
Decimal Places
1
Maximum
VM_SPEED_FREQ_REF
Units
Update Rate
4ms write
Decimal Places
1
Maximum
VM_SPEED_FREQ_REF
Units
Update Rate
4ms read
Decimal Places
1
Maximum
VM_POSITIVE_REF_CLAMP1
Units
Update Rate
Background read
Decimal Places
1
Maximum
VM_NEGATIVE_REF_CLAMP1
Units
Update Rate
Background read
Decimal Places
1
23