Parameter
01.054 Fire Mode Activate
Short description
Set to 1 to activate fire mode
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, NC
Fire Mode Activate (01.054) cannot be written directly, but it can be controlled from a digital input. This prevents fire mode from being enabled from the
keypad, comms or an option module.
Fire mode is intended for purging air from a ventilation system in the event of a fire. All trips are either disabled or are automatically reset after 1s. The use
of fire mode can result in damage to the drive, and so if fire mode is enabled and any trip is initiated an indication that cannot be reset by the user is stored
in Potential Drive Damage Conditions (10.106). For Open-loop, RFC-A or RFC-S modes fire mode is activated and if Fire Mode Reference (01.053) has a
non-zero value and Fire Mode Activate (01.054) = 1. When fire mode is activated normal drive operation is overridden as follows.
1. Pre-ramp Reference (01.003) is forced to the value in Fire Mode Reference (01.053).
2. The Final drive enable is forced to be active provided the safe torque off hardware input will allow the drive to be enabled. The Final drive run is
forced to be active.
3. Forward Limit Switch (06.035) and Reverse Limit Switch (06.036) are disabled.
4. The hand/off/auto system is disabled. If this system is in the hand state when fire mode is activated it will be forced to the off state, so that hand
state is not active when fire mode is de-activated.
5. Keypad control mode is disabled.
6. All latched states in the sequencer (Menu 6) are reset.
For Regen mode fire mode is activated if Fire Mode Activate (01.054) = 1. When fire mode is activated the Final drive enable is forced to be active provided
the safe torque off hardware input will allow the drive to be enabled.
If the drive is in the tripped state when fire mode is activated the trip is reset and then only the trips listed in the table below can be initiated whilst fire mode
is active. If any of the trips shown as resettable occur, the drive will attempt to automatically reset the trip after 1s.
Trip number
Trip
2
Over Volts
3
OI ac
4
OI Brake
5
PSU
9
PSU 24V
21
OHt Inverter
31
EEPROM Fail
36
User Save
37
Power Down Save
109
OI dc
200
Slot1 HF
205
Slot2 HF
210
Slot3 HF
217-249
250
Slot4 HF
34
Maximum
Units
Update Rate
Decimal Places
Resettable
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
No
No
No
No
No
1
Background read
0
Powerdrive F300 Parameter Reference Guide