Download Print this page

Emerson Powerdrive F300 Reference Manual page 203

Hide thumbs Also See for Powerdrive F300:

Advertisement

Parameter
11.029 Software Version
Short description
Displays the software version in the drive
Mode
Open‑Loop
Minimum
0
Default
Type
32 Bit Volatile
Display Format
Version
Coding
RO, ND, NC, PT
Software Version (11.029) displays the drive software version number as a decimal number wwxxyyzz. A keypad will display the value in this parameter
as ww.xx.yy.zz.
Parameter
11.030 User Security Code
Short description
Defines the user security code of the drive
Mode
Open‑Loop
Minimum
0
Default
Type
32 Bit User Save
Display Format
Standard
Coding
RW, ND, NC, PT
See User Security Status (11.044).
Parameter
11.031 User Drive Mode
Short description
Defines the mode of the drive
Mode
Open‑Loop
Minimum
1
Default
Type
8 Bit Volatile
Display Format
Standard
Coding
RW, TE, ND, NC, PT
Value
Text
1
Open-loop
2
RFC-A
3
RFC-S
User Drive Mode (11.031) is set to the current drive mode at power-up. The user can change the drive mode as follows:
1. Set Parameter mm.000 (mm.000) to 1253, 1254, 1255 or 1256
2. Change User Drive Mode (11.031) to the required mode
3. Initiate a drive reset
Provided Drive Active (10.002) = 0 the drive will change to the new drive mode, and then load and save parameters to non-volatile memory.
If Parameter mm.000 (mm.000) is not set to one of the specified values then the drive mode does not change on drive reset. The value in Parameter
mm.000 (mm.000) determines which defaults are loaded as follows.
Parameter mm.000 (mm.000)
1253
1254
1255
1256
Parameter
11.033 Drive Rated Voltage
Short description
Displays the voltage rating of the drive
Mode
Open‑Loop
Minimum
0
Default
Type
8 Bit Volatile
Display Format
Standard
Coding
RO, TE, ND, NC, PT
Value
Text
0
200V
1
400V
2
575V
3
690V
Drive Rated Voltage (11.033) shows the voltage rating of the drive.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Defaults loaded
50Hz defaults to all menus
60Hz defaults to all menus
50Hz defaults to all menus except 15 to 20 and 24 to 28
60Hz defaults to all menus except 15 to 20 and 24 to 28
Maximum
Units
Update Rate
Decimal Places
99999999
Power-up write
0
2147483647
Background read
0
3
Background read
0
3
Power-up write
0
203