Trip
User Trip 153
Value
153
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 154
Value
154
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 155
Value
155
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 156
Value
156
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 157
Value
157
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 158
Value
158
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
User Trip 159
Value
159
Short description
This trip is not used by the drive and can be used for a user trip.
Trip
Voltage Range
Value
169
Short description
This trip is initiated if the Regen Minimum Voltage is set to a non-zero value and the supply voltage is outside the range defined by Regen Maximum Voltage for
more than 100ms.
Recommended actions:
Ensure the supply voltage is operating within the drive specification.
Ensure Regen Minimum Voltage and Regen Maximum Voltage are set correctly.
Check the supply voltage waveform using an oscilloscope.
Reduce the level of supply disturbance.
Set Regen Maximum Voltage to zero to disable this trip.
Trip
Watchdog
Value
30
Short description
This trip indicates that the control word watchdog has been enabled and has timed out.
342
Powerdrive F300 Parameter Reference Guide