Download Print this page

Emerson Powerdrive F300 Reference Manual page 104

Hide thumbs Also See for Powerdrive F300:

Advertisement

Parameter
06.066 Low Under Voltage Threshold
Short description
Defines the low under voltage threshold
Mode
Open‑Loop
Minimum
−VM_LOW_UNDER_VOLTS
Default
See exceptions below
Type
16 Bit User Save
Display Format
Standard
Coding
RW, VM, RA
Voltage
Default Value
200V
175
400V
330
575V
435
690V
435
See Standard Under Voltage Threshold (06.065).
Parameter
06.067 Low Under Voltage Threshold Select
Short description
Set to 1 to use the low under voltage threshold
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
See Standard Under Voltage Threshold (06.065). Also see User Supply Select (06.072) for details of when and how drive parameters can be saved, and
when a User 24V trip can occur.
Parameter
06.068 Backup Supply Mode Enable
Short description
Set to 1 to enable the backup supply mode
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
See Standard Under Voltage Threshold (06.065). Also see User Supply Select (06.072) for details of when and how drive parameters can be saved, and
when a User 24V trip can occur.
Parameter
06.069 Under-voltage System Contactor Close
Short description
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See Standard Under Voltage Threshold (06.065).
Parameter
06.070 Under-voltage System Contactor Closed
Short description
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit Volatile
Display Format
Standard
Coding
RW
See Standard Under Voltage Threshold (06.065).
104
Maximum
VM_LOW_UNDER_VOLTS
Units
V
Update Rate
Background read
Decimal Places
0
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
1
Units
Update Rate
4ms write
Decimal Places
0
Maximum
1
Units
Update Rate
4ms read
Decimal Places
0
Powerdrive F300 Parameter Reference Guide