Sub-trip
Reason
1
Divide by zero
2
Undefined trip
Attempted fast parameter access set-up with non-existent
3
parameter
4
Attempted access to non-existent parameter
5
Attempted write to read-only parameter
6
Attempted an over-range write
7
Attempted read from write-only parameter
The image has failed because either its CRC is incorrect,
30
or there are less than 6 bytes in the image or the image
header version is less than 5.
The image requires more RAM for heap and stack than
31
can be provided by the drive.
The image requires an OS function call that is higher than
32
the maximum allowed.
33
The ID code within the image is not valid
The timed task has not completed in time and has been
40
suspended.
Undefined function called, i.e. a function in the host
41
system vector table that has not been assigned.
52
Customisable menu table CRC check failed
53
Customisable menu table changed
80
*Image is not compatible with the control board
*Image is not compatible with the control board serial
81
number
Image has detected and prevented attempted pointer
100
access outside of the IEC task's heap area.
Image has detected and prevented misaligned pointer
101
usage.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Comments
Occurs when the drive powers-up or the image is
programmed. The image tasks will not run.
As 30.
As 30.
As 30.
Onboard User Program: Enable (11.047) is reset
to zero when the trip is initiated.
As 40.
As 30.
Occurs when the drive powers-up or the image is
programmed and the table has changed. Defaults
are loaded for the user program menu and the trip
will keep occurring until drive parameters are
saved.
Initiated from within the image code.
As 80.