Current limiting on motor overload
When the Motor Protection Accumulator (04.019) reaches 100.0% the current limit is limited to (K
the Motor Protection Accumulator (04.019) falls below 95.0%. (K
Drive thermal monitoring current limiting
If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% the current limit is modified as follows:
Final Current Limit (04.018) = Current limit x (100% - Percentage Of Drive Thermal Trip Level (07.036)) / 10%
If both of the above attempt to reduce the final current limit the lowest calculated value of current limit is used.
This system has the effect of reducing the current limit to zero at the point where the drive should be tripped because its thermal monitoring has
reached a trip threshold. This is intended to limit the load on the drive to prevent it from tripping when supplying a load that increases with speed and
does not include rapid transients.
Parameter
04.017 Magnetising Current
Short description
Shows the instantaneous level of magnetising current
Mode
Open‑Loop
Minimum
−VM_DRIVE_CURRENT
Default
Type
32 Bit Volatile
Display Format
Standard
Coding
RO, FI, VM, ND, NC, PT
Id, Magnetising Current (04.017) is the instantaneous level of magnetising current scaled so that it represents the r.m.s. level of magnetising current
under steady state conditions.
Parameter
04.018 Final Current Limit
Short description
Shows the final current limit that is applied to the torque producing current
Mode
Open‑Loop
Minimum
−VM_TORQUE_CURRENT
Default
Type
16 Bit Volatile
Display Format
Standard
Coding
RO, VM, ND, NC, PT
Final Current Limit (04.018) is the current limit level that is applied to give the Final Current Reference (04.004).
Parameter
04.019 Motor Protection Accumulator
Short description
Shows the level of the motor protection accumulator
Mode
Open‑Loop
Minimum
0.0
Default
Type
16 Bit Power Down Save
Display Format
Standard
Coding
RO, ND, NC, PT
See Motor Thermal Time Constant 1 (04.015).
62
is defined in the description of Motor Thermal Time Constant 1 (04.015).)
1
Maximum
VM_DRIVE_CURRENT
Units
A
Update Rate
250µs write
Decimal Places
3
Maximum
VM_TORQUE_CURRENT
Units
%
Update Rate
4ms write
Decimal Places
1
Maximum
100.0
Units
%
Update Rate
Background write
Decimal Places
1
– 0.05) x 100.0%. This limitation is removed when
1