Parameter
07.013 Analog Input 2 Invert
Short description
Inverts the signal for analog input 2
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).
Parameter
07.014 Analog Input 2 Destination
Short description
Defines the output parameter for analog input 2
Mode
Open‑Loop
Minimum
0.000
Default
1.037
Type
16 Bit User Save
Display Format
Standard
Coding
RW, DE, PT, BU
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).
Parameter
07.019 Analog Output 1 Source
Short description
Defines the input parameter for analog output 1
Mode
Open‑Loop
Minimum
0.000
Default
5.001
Type
16 Bit User Save
Display Format
Standard
Coding
RW, PT, BU
Analog Output 1 Source (07.019) defines the source parameter for analog output 1. The value of the source parameter is scaled with
Analog Output 1 Scaling (07.020) and if the scaling is greater than 1.000 the value is clamped between -100% and +100% or between 0% and 100%
depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules for
parameter routing do not apply, but the scaling always makes -100% to +100% correspond to the range from minus source parameter maximum to plus
source parameter maximum, and 0% corresponds to the source parameter value of zero. This means for example that a parameter with a minimum of 1
and a maximum of 10 will produce an output that changes from 10% to 100% as the parameter is change from minimum to maximum.
The outputs provided with different hardware are given in the table below.
Internal I/O Identifier
(11.068)
0: Standard Analogue and
Digital I/O
1: Basic I/O
2: HVAC Analogue and
Digital I/O
The output mode is defined by Analogue Output 1 Mode (07.021) as shown in the table below.
Analogue Output 1 Mode
Standard Analogue and
(07.021)
Digital I/O
Volt
-10V to + 10V
0-20mA
Not possible
20-0mA
Not possible
4-20mA
Not possible
20-4mA
Not possible
 
Parameter
07.020 Analog Output 1 Scaling
Short description
Defines the scaling factor for analog output 1
Mode
Open‑Loop
Minimum
0.000
Default
1.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Analog Output 1 Source (07.019).
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Analogue Output 1
Analogue Output 2
Bipolar Voltage
Bipolar Voltage
No output
No output
Unipolar Voltage or
Unipolar Voltage or
Current
Current
HVAC Analogue and
Digital I/O
0V to +10V
0mA to 20mA
20mA to 0mA
4mA to 20mA
20mA to 4mA
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
Maximum
59.999
Units
Update Rate
Drive reset read
Decimal Places
3
Maximum
59.999
Units
Update Rate
Drive reset read
Decimal Places
3
Maximum
10.000
Units
Update Rate
Background read
Decimal Places
3
117