Sub-
Reason
trip
1
Divide by zero
2
Undefined trip
Attempted fast parameter access set-up with
3
non-existent parameter
4
Attempted access to non-existent parameter
5
Attempted write to read-only parameter
6
Attempted and over-range write
7
Attempted read from write-only parameter
The image has failed because either its CRC is
incorrect, or there are less than 6 bytes in the
30
image or the image header version is less than
5.
The image requires more RAM for heap and
31
stack than can be provided by the drive.
The image requires an OS function call that is
32
higher than the maximum allowed.
The timed task has not completed in time and
40
has been suspended.
Undefined function called, i.e. a function in the
41
host system vector table that has not been
assigned.
Core menu customisation table CRC check
51
failed
52
Customisable menu table CRC check failed
53
Customisable menu table changed
The option module fitted in slot 1 is not allowed
61
with the derivative image.
The option module fitted in slot 2 is not allowed
62
with the derivative image.
The option module fitted in slot 3 is not allowed
63
with the derivative image.
The option module fitted in slot 4 is not allowed
64
with the derivative image.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Comments
Occurs when the drive powers-up or the image is programmed.
The image tasks will not run.
As 30.
As 30.
As 40.
As 30.
As 30.
Occurs when the drive powers-up or the image is programmed and
the table has changed. Defaults are loaded for the derivative menu
and the trip will keep occurring until drive parameters are saved.
As 30.
As 30.
As 30.
As 30.