fitted or the voltage is below the minimum threshold.
Parameter
10.064 Remote Keypad Battery Low
Short description
Indicates that the real time clock battery in the remote keypad is low
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Remote Keypad Battery Low (10.064) is set to one when a keypad is connected to the drive user comms port with an internal real-time clock and the
battery is not fitted or the voltage is below the minimum threshold.
Parameter
10.065 Auto-tune Active
Short description
Indicates that an auto-tune sequence is active
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Auto-tune Active (10.065) is set to one while an auto-tune sequence is active.
Parameter
10.067 Fire Mode Active
Short description
Indicates that fire mode is enabled and active
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Fire Mode Active (10.067) is set to one when fire mode is enabled and active.
Parameter
10.068 Hold Drive Healthy on Under Voltage
Short description
Set to hold drive healthy if the drive is in the under voltage state
Mode
Open‑Loop
Minimum
0
Default
0
Type
1 Bit User Save
Display Format
Standard
Coding
RW
Hold Drive Healthy on Under Voltage (10.068) can be used to hold the drive healthy active (Drive Healthy (10.001) = 1 and not flash the status LED on
the front of the drive) when the drive is in the under voltage state (Under Voltage Active (10.016) = 1).
If Hold Drive Healthy on Under Voltage (10.068) = 0 and Under Voltage Active (10.016) = 1, then Drive Healthy (10.001) will be set to 0 and the status
LED on the front of the drive will flash.
If Hold Drive Healthy on Under Voltage (10.068) = 1, Under Voltage Active (10.016) = 1 and the drive is not tripped (i.e. Drive Status (10.101) does not
equal 9), then Drive Healthy (10.001) will be set to 1 and the status LED on the front of the drive will not flash.
If the drive is tripped then Drive Healthy (10.001) will be set to 0 and the status LED will flash independent of what Hold Drive Healthy on Under Voltage
(10.068) is set to.
Parameter
10.069 Additional Status Bits
Short description
Shows the additional status bits for the drive
Mode
Open‑Loop
0
Minimum
(Display: 0000000000)
Default
Type
16 Bit Volatile
Display Format
Binary
Coding
RO, ND, NC, PT
The bits in Additional Status Bits (10.069) mirror the status bits parameters as shown below. Where the parameters do not exist in any mode the bit
remains at zero.
188
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
1023
Maximum
(Display: 1111111111)
Units
Update Rate
Background write
Decimal Places
0
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00

Advertisement