Emerson Powerdrive F300 Reference Manual page 170

Hide thumbs Also See for Powerdrive F300:

Advertisement

Parameter
10.006 At Speed
Short description
Indicates that the drive is running at the set speed
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See At Speed Lower Limit (03.006).
Parameter
10.007 Above Set Speed
Short description
Indicates that the drive is running above the set speed
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See At Speed Lower Limit (03.006).
Parameter
10.008 Rated Load Reached
Short description
Indicates that rated load has been reached
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Rated Load Reached (10.008) is set to one when the torque producing current is at or above its rated level. This condition is detected when the
modulus of Percentage Load (04.020) is greater or equal to 100.0%. It should be noted that this is an indication based on the level of current and not
torque, which means that if field weakening is active a value of one in Rated Load Reached (10.008) does not necessarily mean that the motor is
producing rated torque.
Parameter
10.009 Current Limit Active
Short description
Indicates that the current limit is active
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Current Limit Active (10.009) is set to one if the current limit is active. It should be noted that the current limit system is used in RFC-A and RFC-S
modes when standard ramp control is active (Ramp Mode (02.004)), or supply loss control is in ramp stop or limit stop mode (Supply Loss Mode
(06.003)). Therefore Current Limit Active (10.009) is likely to change to one under these conditions, even if the user defined current limits are not active.
Parameter
10.010 Regenerating
Short description
Indicates that power is being transferred from the motor to the drive
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Regenerating (10.010) is set to one if power is being transferred from the motor to the drive.
Parameter
10.011 Braking IGBT Active
Short description
Indicates that the braking IGBT is active
Mode
Open‑Loop
Minimum
0
Default
Type
1 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
Braking IGBT Active (10.011) is set to one if the braking IGBT is active. As the braking IGBT active periods may be short, each time the braking IGBT is
170
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
4ms write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Maximum
1
Units
Update Rate
Background write
Decimal Places
0
Powerdrive F300 Parameter Reference Guide