Troubleshooting with the Basic Operator Panel

If the display shows a fault or warning code, please refer to Reference Manual.
If the motor fails to start when the ON command has been given:
Check that P0010 = 0.
Check that a valid ON signal is present.
Check that P0700 = 2 (for digital input control) or
Check that the setpoint is present (0 to 10V on Terminal 3) or the setpoint has
been entered into the correct parameter, depending upon the setpoint source
(P1000). See the Parameter List for further details.
If the motor fails to run after changing the parameters, set P0010 = 30 then P0970
= 1 and press P to reset the inverter to the factory default parameter values.
Now use a switch between terminals 5 and 8 on the control board. The drive
should now run to the defined setpoint by analogue input.
Note
Motor data must relate to the inverter data power range and voltage.
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0
P0700 = 1 (for BOP control).