Issue 04/02
6

Troubleshooting

WARNING
♦ ♦ ♦ ♦ Repairs on equipment may only be carried out by Siemens Service, by repair
centers authorized by Siemens or by qualified personnel who are thoroughly
acquainted with all the warnings and operating procedures contained in this
manual.
♦ ♦ ♦ ♦ Any defective parts or components must be replaced using genuine Siemens
authorised parts.
♦ ♦ ♦ ♦ Risk of electric shock. The DC link capacitors remain charged for five minutes
after power has been removed. It is not permissible to open the equipment
until 5 minutes after the power has been removed.
6.1

Troubleshooting with the Standard Inverter LED

The following is a description of the fault and warning indications given by the LED
on the Standard Inverter:
Ø Inverter Off/No supply:
Ø Power On/Ready:
Ø Inverter Running OK:
Ø General Warning:
Ø Fault Condition:
6.2

Troubleshooting with the Operator Panel (OP)

If the display shows a fault or warning code, please refer to Section 6.3.
If the motor fails to start when the ON command has been given:
Ø Check that P0010 = 0.
Ø Check that a valid ON signal is present.
Ø Check that P0700 = 2 (for digital input control) or
Ø Check that the setpoint is present (0 to 10V on Terminal 7) or the setpoint has
been entered into the correct parameter, depending upon the setpoint source
(P1000). See the Parameter List for further details.
If the motor fails to run after changing the parameters, set P0010 = 30 then P0970
= 1 and press P to reset the inverter to the factory default parameter values.
Now use a switch between cobtrol terminals 1 and 4. The drive should now run to
the defined setpoint by analogue input.
NOTICE
Motor data must relate to the inverter data power range and voltage.
MICROMASTER 410
Operating Instructions
6SE6400-5EA00-0BP0
No LED lit.
1000 ms On / 1000 ms Off
Steady LED
500 ms On / 200 ms Off
100 ms On / 100 ms Off
P0700 = 1 (for OP control).
6 Troubleshooting