Connection to Sinteso / Cerberus PRO panels
18.3

Detectors connected to Sinteso / Cerberus PRO panel

18.3.1 Connection variant 3:
94
Building Technologies
Fire Safety
b. select "Autom. exting. release blockable from Sinteso / Cerberus PRO"
c. select "Show blocking of autom. Exting. release on Sinteso / Cerberus
PRO operating terminal"
d. select "Resetable from Sinteso /Cerberus PRO"
e. select "Enable" and configure "Reset time" = 10 s
Assign XC10 zone inputs elements (an FDCIO222 is installed inside the XC10):
4. assign element 1:Input 'Discharged' to FDCIO IN1
5. assign element 2:Input 'Fault' to FDCIO IN2 and select "Input inverted" in
Hardware tab
6. assign element 3:Input 'Pre-alarm' to FDCIO IN3
7. assign element 4:Input 'Blocked' to FDCIO IN14
Assign XC10 zone "Block autom." output element:
7. assign element 2:Output 'Block autom." to FDCIO OUT 2 (Relay B)
Assign XC10 zone "Reset" output element:
XC10 needs 2 reset pulses to reset completely. The first pulse resets the buzzer and sounders; the
second pulse resets the panel. With the following configuration, a single Reset operation on the Sinteso
/ Cerberus PRO panel generates 2 reset pulses on the XC10.
8. create a fire control group named "Training Center - Room Spirit 1"
9. create a fire control named "XC10 Reset pulse 1"
a. formula: "- - - ALL OR - - -"
b. activation delay: 0s
c. deactivation delay 0s
d. activation timeout: Enable / 3s
e. cause: 1:Output 'Reset' XC10 Zone "Extinguishing" activated
f.
effect: no effects
10. create a fire control named "XC10 Reset pulse 2"
a. formula: "-1"
b. activation delay: 3s
c. deactivation delay 0s
d. activation timeout: Enable / 3s
e. cause: Fire Control "XC10 Reset pulse 1" activated
f.
effect: no effects
11. create a fire control named "XC10 Reset pulse 1+2"
a. formula: "- - - ALL OR - - -"
b. activation delay: 0s
c. deactivation delay 0s
d. activation timeout: Disabled
e. cause1: Fire Control "XC10 Reset pulse 1" activated
f.
cause2: Fire Control "XC10 Reset pulse 2" activated
g. effect: assign to FDCIO OUT 1 (Relay A)
Following XC10 zone messages can be displayed:
- "Exting. discharged"
- "Fault"
- "Exting.pre-alarm"
- "Aut+man ext.OFF XC"
- "Aut.ext.OFF XC"
- "Aut.ext.OFF FC" (XC10 blocked from the Sinteso / Cerberus PRO panel)
Following controls are possible from the Sinteso / Cerberus PRO panel:
- Reset
- Block autom.
- Alarm zone 1
A6V10257473_e_en_--