Connection to Sinteso / Cerberus PRO panels
92
Building Technologies
Fire Safety
Fig. 42
Detectors connected to XC10 control panel – Variant 1
Jumper X14 position (relay contact 5) must be changed from factory setting to the right position (NC
contact)
For this variant, step 37 option 01 must be selected (Reset at any time). Due to
EN12094-1 clause 4.12.2, it is imperative to ensure that the reset operation from the
CAUTION
Sinteso / Cerberus PRO panel is not allowed during flooding time. If this cannot be
ensured, this connection variant is not allowed.
Configuration example using FXS engineering tool:
Create an XC10 zone:
1. create an area named "Siemens Training Center"
2. create a section named "Room Spirit 1"
3. under this section
a. create an XC10 Zone named "Extinguishing"
b. select "Autom. exting. release blockable from Sinteso / Cerberus PRO"
c. select "Autom.+man. exting. release blockable from FS720"
d. select "Show blocking of autom. Exting. release on Sinteso / Cerberus
PRO operating terminal"
e. select "Resetable from Sinteso /Cerberus PRO"
f.
select "Enable" and configure "Reset time" = 10 s
Assign XC10 zone inputs elements (an FDCIO222 is installed inside the XC10):
4. assign element 1:Input 'Discharged' to FDCIO IN1
5. assign element 2:Input 'Fault' to FDCIO IN2 and select "Input inverted" in
Hardware tab
6. assign element 3:Input 'Pre-alarm' to FDCIO IN3
7. assign element 4:Input 'Blocked' to FDCIO IN14
Assign XC10 zone output element:
8. assign element 1:Output 'Reset' to FDCIO OUT 1 (Relay A)
A6V10257473_e_en_--
2015-03-04